Difference between revisions of "Plant Boundary Definition and Partitioning (Task 1)"
Line 15: | Line 15: | ||
* Documentation of the basic features of some or all fire compartments. | * Documentation of the basic features of some or all fire compartments. | ||
− | ==Related | + | ==Related Elements of ASME/ANS PRA Standard== |
Plant Partitioning (PP) | Plant Partitioning (PP) | ||
Revision as of 10:14, 26 November 2018
Contents
Task Overview
Objective
The first step in a Fire PRA is to define the physical boundary of the analysis, and to divide the area within that boundary into analysis compartments.
Purpose
For the purposes of a Fire Probabilistic Risk Assessment (PRA), the plant is divided into a number of fire compartments. The analysis then considers the impact of fires in a given compartment, and fires that might impact multiple compartments. This procedure establishes the process for defining the global plant analysis boundary and partitioning of the plant into fire compartments. The product of this task will be a list of plant fire compartments in the nuclear power plant under analysis.
Scope
The work package developed to support the plant-partitioning task should address the following issues:
- Basis for and identification of the limits of the selected global plant boundary,
- Basis for and results of partitioning the selected global plant boundary into fire compartments,
- Mapping of fire compartments to plant fire areas defined in regulatory compliance activities, and
- Documentation of the basic features of some or all fire compartments.
Related Elements of ASME/ANS PRA Standard
Plant Partitioning (PP)
Related EPRI 1011989 NUREG/CR-6850 Appendices
None
Supplemental Guidance
There is no supplemental guidance associated with Plant Boundary Definition and Partitioning (Task 1).