Difference between revisions of "Detailed Fire Modeling (Task 11)"
| Line 26: | Line 26: | ||
==Related EPRI 1011989 NUREG/CR-6850 Appendices== | ==Related EPRI 1011989 NUREG/CR-6850 Appendices== | ||
| + | Appendix E, Appendix for Chapters 8 and 11, Severity Factors | ||
| + | Appendix F, Appendix for Chapter 8, Walkdown Forms | ||
| + | Appendix G, Appendix for Chapters 8 and 11, Heat Release Rates | ||
| + | Appendix H, Appendix for Chapters 8 and 11, Damage Criteria | ||
| + | Appendix L, Appendix for Chapter 11, Main Control Board Fires | ||
| + | Appendix M, Appendix for Chapter 11, High Energy Arcing Faults | ||
| + | Appendix N, Appendix for Chapter 11, Hydrogen Fires | ||
| + | Appendix O, Appendix for Chapter 11, Turbine Generator Fires | ||
| + | Appendix P, Appendix for Chapter 11, Detection And Suppression Analysis | ||
| + | Appendix Q, Appendix for Chapter 11, Passive Fire Protection Features | ||
| + | Appendix R, Appendix for Chapter 11, Cable Fires | ||
| + | Appendix S, Appendix for Chapter 11, Fire Propagation To Adjacent Cabinets | ||
| + | Appendix T, Appendix for Chapter 11, Smoke Damage | ||
==Supplemental Guidance== | ==Supplemental Guidance== | ||
Revision as of 16:11, 13 September 2017
Contents
Task Overview
Background
This task describes the method to examine the consequences of a fire. This includes consideration of scenarios involving single compartments, multiple fire compartments, and the main control room. Factors considered include initial fire characteristics, fire growth in a fire compartment or across fire compartments, detection and suppression, electrical raceway fire barrier systems, and damage from heat and smoke. Special consideration is given to turbine generator (T/G) fires, hydrogen fires, high-energy arcing faults, cable fires, and main control board (MCB) fires. There are considerable improvements in the method for this task over the EPRI FIVE and Fire PRA Implementation Guide in nearly all technical areas.
Purpose
In the preceding tasks, the analyses were organized around compartments, assuming that a fire would have widespread impact within the compartment. In Task 11, for those compartments found to be potentially risk-significant (i.e., unscreened compartments), a detailed analysis approach is provided. As part of the detailed analysis, fire growth and propagation is modeled and possibility of fire suppression before damage to a specific target set is analyzed.
The detailed fire modeling process generally follows a common step structure, but the details of the analyses often vary depending on the specifics of the postulated fire scenario. This chapter provides separate procedures for three general categories of fire scenarios: fires affecting target sets located inside one compartment (discussed in Section 11.5.1); fires affecting the main control room (MCR; Section 11.5.2); and fires affecting target sets located in more than one fire compartment (multicompartment fire analysis; Section 11.5.3).
Task 11 provides final estimates for the frequency of occurrence of fire scenarios involving a specific fire ignition source failing a predefined target set before fire protection succeeds in protecting the target set. This result is combined in the final quantification steps that follow this task, with the CCDP/CLERP given failure of the target set to estimate the CDF/LERF contribution for each fire scenario. The CCDP/CLERP may include modified human error probabilities based on fire scenario specifics
Scope
Detailed fire modeling encompasses an analysis of the physical fire behavior (i.e., fire growth and propagation analysis), equipment damage, fire detection, and fire suppression. The fire scenarios to analyze as part of this detailed analysis task are divided into three categories:
- General single compartment fire scenarios. This general category covers fire scenarios damaging target sets located within the same compartment, exclusive of those scenarios within or impacting the MCR. In general, in this category, the fire ignition source is in the same compartment as the target set. The majority of fire scenarios analyzed generally falls into this category. The procedures applicable to the analysis of these fire scenarios are presented in Section 11.5.1.
- MCR fire scenarios. This general category covers all fires that occur within the MCR. This category also covers scenarios involving fires in compartments other than the MCR that may force MCR abandonment. The MCR analysis procedures are presented in Section 11.5.2.
- Multicompartment fire scenarios: This general category covers all fire scenarios where it is postulated that a fire may spread from one compartment to another and damage target elements in multiple compartments. In this category of scenarios, damaging effects of a fire (e.g., heat) are assumed to spread beyond the compartment of fire origin. The multicompartment fire analysis procedures are presented in Section 11.5.3.
A detailed fire modeling analysis is performed for each fire scenario in each unscreened fire compartment. For many compartments, it may be appropriate to develop several fire scenarios to appropriately represent the range of unscreened fire ignition sources (i.e., scenarios that would not screen out in Task 8) that might contribute to the fire risk. Detailed fire modeling may utilize a range of tools to assess fire growth and damage behavior, and the fire detection and suppression response, for specific fire scenarios.
The ultimate output of Task 11 is a set of fire scenarios, frequency of occurrence of those scenarios, and a list of target sets (in terms of fire PRA components) associated with the scenarios. For scenarios involving the MCR, the possibility of forced abandonment is also noted. Note that a fire scenario represents a specific chain of events starting with ignition of a fire ignition source, propagation of the fire effects to other items, and possibility of damaging a set of items identified as target set before successful fire suppression.
Related Element(s) of ASME/ANS PRA Standard, ASME-RA-Sb-2013
Fire Scenario Selection (FSS)
Related EPRI 1011989 NUREG/CR-6850 Appendices
Appendix E, Appendix for Chapters 8 and 11, Severity Factors Appendix F, Appendix for Chapter 8, Walkdown Forms Appendix G, Appendix for Chapters 8 and 11, Heat Release Rates Appendix H, Appendix for Chapters 8 and 11, Damage Criteria Appendix L, Appendix for Chapter 11, Main Control Board Fires Appendix M, Appendix for Chapter 11, High Energy Arcing Faults Appendix N, Appendix for Chapter 11, Hydrogen Fires Appendix O, Appendix for Chapter 11, Turbine Generator Fires Appendix P, Appendix for Chapter 11, Detection And Suppression Analysis Appendix Q, Appendix for Chapter 11, Passive Fire Protection Features Appendix R, Appendix for Chapter 11, Cable Fires Appendix S, Appendix for Chapter 11, Fire Propagation To Adjacent Cabinets Appendix T, Appendix for Chapter 11, Smoke Damage