Difference between revisions of "Fire Ignition Frequency (Task 6)"

From FirePRA
Jump to navigation Jump to search
 
(62 intermediate revisions by the same user not shown)
Line 12: Line 12:
 
* Plant specific fire event data review and generic fire frequency update using Bayesian approach,
 
* Plant specific fire event data review and generic fire frequency update using Bayesian approach,
 
* Equipment (ignition source) count by compartment,  
 
* Equipment (ignition source) count by compartment,  
−
* Apportioning of ignition frequencies according to compartment-specific configurations, and  
+
* Apportioning of ignition frequencies according to compartment-specific configurations, and  
−
* Uncertainty considerations in the fire frequencies.  
+
* Uncertainty considerations in the fire frequencies.
  
−
==Related Element(s) of ASME/ANS PRA Standard, ASME-RA-Sb-2013==
+
==Related Element of ASME/ANS PRA Standard==
 
Fire Ignition Frequency (IGN)
 
Fire Ignition Frequency (IGN)
 +
 +
==Related EPRI 1011989 NUREG/CR-6850 Appendices==
 +
Appendix C, Appendix for Chapter 6, Determination of Generic Fire Frequencies
 +
 +
Appendix F, Appendix for Chapter 8, Walkdown Forms
  
 
==Current FPRA Counting Guidance and Fire Ignition Frequencies==
 
==Current FPRA Counting Guidance and Fire Ignition Frequencies==
  
 +
Table 6-1 presents relevant information such as bin, ignition source, counting guidance, and mean fire ignition frequency for ignition sources counted in the Fire PRA. In many cases, the counting guidance provided in NUREG/CR-6850 has been supplemented by additional guidance including formally published in NUREG/CR-6850 Supplement 1 and through the frequently asked questioned (FAQ) process. Links to the counting guidance is provided in the "Counting Reference" column. Similarly, the fire ignition frequencies published in NUREG/CR-6850 are no longer the most current. A second set of fire ignition frequencies was published in NUREG/CR-6850 Supplement 1 (Chapter 10, FAQ 08-0048). A [https://www.nrc.gov/docs/ML1513/ML15134A046.pdf memo on May 14, 2015 from the NRC], clarified that the fire ignition frequencies in NUREG/CR-6850 Supplement 1 (FAQ 08-0048) should be replaced with the most current guidance in EPRI 3002002936 (NUREG-2169). 
  
 +
'''Table 6-1: Fire Ignition Sources, Counting Guidance, and Ignition Frequencies'''
 
{| class="wikitable"
 
{| class="wikitable"
 
|-
 
|-
Line 67: Line 74:
 
| Main Control Board
 
| Main Control Board
 
| A control room typically consists of one or two (depending on the number of units) main control boards as the central element of the room.
 
| A control room typically consists of one or two (depending on the number of units) main control boards as the central element of the room.
−
| Each main control board, typically consisting of the main horseshoe and nothing else, is counted separately. This bin may also include "benchboard" panels that are detached from, but directly in front of, the main horseshoe (at some plants such panels are referred to as "consoles"). FAQ-14-008 also clarified that the rear side of the MCB may be treated as part of the MCB if both the rear and front sides are connected together as a single enclosure (including a continuous overhead, or by an overhead with penetrations or vents along it longitudinally, cabinet ceiling, or cables connecting the front and back sides of the MCB).  
+
| Each main control board, typically consisting of the main horseshoe and nothing else, is counted separately. This bin may also include "benchboard" panels that are detached from, but directly in front of, the main horseshoe (at some plants such panels are referred to as "consoles"). FAQ-14-0008 also clarified that the rear side of the MCB may be treated as part of the MCB if both the rear and front sides are connected together as a single enclosure (including a continuous overhead, or by an overhead with penetrations or vents along it longitudinally, cabinet ceiling, or cables connecting the front and back sides of the MCB).  
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
[https://www.epri.com/#/pages/product/000000000001019259/?lang=en-US FAQ 06-0018, Section 5 of Supplement 1]
 
[https://www.epri.com/#/pages/product/000000000001019259/?lang=en-US FAQ 06-0018, Section 5 of Supplement 1]
  
−
[https://www.nrc.gov/docs/ML1419/ML14190B307.pdf FPRA-FAQ 14-0008]
+
[https://www.nrc.gov/docs/ML1419/ML14190B307.pdf FAQ 14-0008]
−
| 4.91E-03
+
| 2.05E-3
−
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
+
| [https://www.epri.com/#/pages/product/000000003002016052/ NUREG-2178 Vol 2 / EPRI 3002016052]
 
|-
 
|-
 
| 5
 
| 5
Line 84: Line 91:
 
[https://www.nrc.gov/docs/ML1234/ML12346A488.pdf FAQ 12-0064]
 
[https://www.nrc.gov/docs/ML1234/ML12346A488.pdf FAQ 12-0064]
  
−
[https://www.nrc.gov/docs/ML1725/ML17258A687.html FPRA-FAQ 16-0010]
+
[https://www.nrc.gov/docs/ML1725/ML17258A687.html FAQ 16-0010]
 
| 7.83E-04
 
| 7.83E-04
 
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
 
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
Line 104: Line 111:
 
| Transients
 
| Transients
 
| General transient combustibles or activities located in the Control Building, Auxiliary Building, or Reactor Building.
 
| General transient combustibles or activities located in the Control Building, Auxiliary Building, or Reactor Building.
−
| The ignition source weighting factor of transient fires is estimated using a ranking scheme that takes into account maintenance activities, occupancy level, and storage of flammable materials.  These steps are outlined in FAQ 12-0064 Section 6.5.7.2. The introduction of developing transient influence factors for smaller spaces than fire compartments is discussed in FAQ 14-0007.  
+
| The ignition source weighting factor of transient fires is estimated using a ranking scheme that takes into account maintenance activities, occupancy level, and storage of flammable materials.  These steps are outlined in FAQ 12-0064 Section 6.5.7.2. Developing transient influence factors for smaller spaces than fire compartments is discussed in FAQ 14-0007.  
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
  
Line 117: Line 124:
 
| Diesel Generators
 
| Diesel Generators
 
| Diesel generators are generally well-defined items that include a set of auxiliary subsystems associated with each engine.  All diesel generators that are included in the electric power recovery model should be counted here. In addition to the normal safety related diesel generators, this may include  the Technical Support Center diesel generators, Security diesel generators, etc. It is recommended that each diesel generator and its subsystems be counted as one unit. The subsystems may include diesel generator air start compressors, air receiver, batteries and fuel storage, and delivery system.  
 
| Diesel generators are generally well-defined items that include a set of auxiliary subsystems associated with each engine.  All diesel generators that are included in the electric power recovery model should be counted here. In addition to the normal safety related diesel generators, this may include  the Technical Support Center diesel generators, Security diesel generators, etc. It is recommended that each diesel generator and its subsystems be counted as one unit. The subsystems may include diesel generator air start compressors, air receiver, batteries and fuel storage, and delivery system.  
−
| Each diesel generator shall be counted separately. It is recommended that the electrical cabinets for engine and generator control that stand separate from the diesel generator be included as part of “Plant-Wide Components - Electrical Cabinets.” Control panels that are attached to engine may be counted as part of the engine.
+
| Each diesel generator should be counted separately. It is recommended that the electrical cabinets for engine and generator control that stand separate from the diesel generator be included as part of “Plant-Wide Components - Electrical Cabinets.” Control panels that are attached to engine may be counted as part of the engine.
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
| 7.81E-03
 
| 7.81E-03
Line 149: Line 156:
 
[https://www.nrc.gov/docs/ML1234/ML12346A488.pdf FAQ 12-0064]
 
[https://www.nrc.gov/docs/ML1234/ML12346A488.pdf FAQ 12-0064]
  
−
[https://www.nrc.gov/docs/ML1725/ML17258A687.html FPRA-FAQ 16-0010]
+
[https://www.nrc.gov/docs/ML1725/ML17258A687.html FAQ 16-0010]
 
| 2.77E-04
 
| 2.77E-04
 
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
 
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
Line 158: Line 165:
 
| Self-ignited cables fires postulated in fire compartments with unqualified cables only or a mix of qualified cables and unqualified cables.  
 
| Self-ignited cables fires postulated in fire compartments with unqualified cables only or a mix of qualified cables and unqualified cables.  
 
| The cable loading of each compartment should be established using the same approach as that for Bin 5, except that, in this case, all plant fire compartments should be taken into account. The cable quantity (either total weight or total combustible load) is typically reported in the Fire Hazards Analysis (FHA). For rooms where detailed fire modeling is necessary FAQ 13-0005 provides guidance on how to calculate a scenario level ignition frequency (by dividing the quantity of cables in the tray on fire by the total quantity of cable in the room).   
 
| The cable loading of each compartment should be established using the same approach as that for Bin 5, except that, in this case, all plant fire compartments should be taken into account. The cable quantity (either total weight or total combustible load) is typically reported in the Fire Hazards Analysis (FHA). For rooms where detailed fire modeling is necessary FAQ 13-0005 provides guidance on how to calculate a scenario level ignition frequency (by dividing the quantity of cables in the tray on fire by the total quantity of cable in the room).   
 +
Consistent with Appendix R of EPRI 1011989, self-ignited cable fire only need to be postulated in compartments which contain unqualified cable types.
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
−
[https://www.nrc.gov/docs/ML1331/ML13319B181.pdf FPRA-FAQ 13-0005]
+
[https://www.nrc.gov/docs/ML1331/ML13319B181.pdf FAQ 13-0005]
  
−
[https://www.nrc.gov/docs/ML1725/ML17258A687.html FPRA-FAQ 16-0010]
+
[https://www.nrc.gov/docs/ML1725/ML17258A687.html FAQ 16-0010]
 
| 7.02E-04
 
| 7.02E-04
 
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
 
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
Line 177: Line 185:
 
| Plant-Wide Components
 
| Plant-Wide Components
 
| Electric Motors
 
| Electric Motors
−
| The electrical motors with power rating greater than 5hp associated with various devices, not including those counted in other bins, are included in this bin. This may include elevator motors, valve motors, etc.   
+
| Electrical motors with a power rating greater than 5hp associated with various devices, not including those counted in other bins, are included in this bin. This may include elevator motors, valve motors, etc.   
 
| Motors (not included those counted in other bins) with a rating greater than 5 HP are counted. Totally enclosed motors should be excluded from the count because the motor housing would prevent the extension of flames outside the motor casing. See FAQ 07-0031 for the additional guidance.
 
| Motors (not included those counted in other bins) with a rating greater than 5 HP are counted. Totally enclosed motors should be excluded from the count because the motor housing would prevent the extension of flames outside the motor casing. See FAQ 07-0031 for the additional guidance.
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
Line 187: Line 195:
 
| Plant-Wide Components
 
| Plant-Wide Components
 
| Electrical Cabinets
 
| Electrical Cabinets
−
| Electrical cabinets represent such items as switchgears, motor control centers, DC distribution panels, relay cabinets, control and switch panels (excluding panels that are part of machinery), fire protection panels, etc.  Electrical cabinets in a nuclear power plant vary significantly in size, configuration, and voltage. Size variation range from small-wall mounted units to large walk-through vertical control cabinets, which can be 20’ to 30’ long. The configuration can vary based on number of components that contribute to ignition, such as relays and circuit cards, and combustible loading, which also affects the fire frequency. Voltages in electrical cabinets vary from low voltage (120 V) panels to 6.9 kV switchgears. Even though it is expected that these features affect the likelihood of fire ignition, from a simple analysis of the event data involving the electrical cabinets, it was determined that the variation by cabinet type did not warrant separate frequency evaluation. Therefore, one fire frequency was estimated for the electrical cabinets.
+
| Electrical cabinets represent such items as switchgears, motor control centers, DC distribution panels, relay cabinets, control and switch panels (excluding panels that are part of machinery), fire protection panels, etc.   
 +
| <div id="IgnBin15"></div>Electrical cabinets in a nuclear power plant vary significantly in size, configuration, and voltage. Size variation range from small-wall mounted units to large walk-through vertical control cabinets, which can be 20’ to 30’ long. The configuration can vary based on number of components that contribute to ignition, such as relays and circuit cards, and combustible loading, which also affects the fire frequency. Voltages in electrical cabinets vary from low voltage (120 V) panels to 6.9 kV switchgear. Even though it is expected that these features affect the likelihood of fire ignition, from a simple analysis of the event data involving the electrical cabinets, it was determined that the variation by cabinet type did not warrant separate frequency evaluation. Therefore, one fire frequency was estimated for the electrical cabinets.
 
The following rules should be used for counting electrical cabinets:  
 
The following rules should be used for counting electrical cabinets:  
 +
 
– Simple wall-mounted panels housing less than four switches may be excluded from the counting process,  
 
– Simple wall-mounted panels housing less than four switches may be excluded from the counting process,  
−
– Well-sealed electrical cabinets that have robustly secured doors (and/or access panels) and that house only circuits below 440V should be excluded from the counting process,  
+
 
−
– Free-standing electrical cabinets should be counted by their vertical segments, and 
+
– Well-sealed electrical cabinets that have robustly secured doors (and/or access panels) and that house only circuits below 440V should be excluded from the counting process, (In this context, the term “well-sealed” means there are no open or unsealed penetrations, there are no ventilation openings, and potential warping of the sides/walls of the panel would not open gaps that might allow an internal fire to escape. “Robustly secured” means that any doors and/or access panels are all fully and mechanically secured and will not create openings or gaps due to warping during an internal fire. For example, a panel constructed of sheet metal sides “tack welded” to a metal frame would not be considered well-sealed because internal heating would warp the side panels allowing fire to escape through the resulting gaps between weld points. A panel with a simple twist-handle latch mechanism would not be considered robustly secured because the twist handle would not prevent warping of the door under fire conditions. In contrast, a water-tight panel whose door/access panel is bolted in place or secured by mechanical bolt-on clamps around its perimeter would be considered both well-sealed and robustly secured.  Also note that panels that house circuit voltages of 440V or greater are counted because an arcing fault could compromise panel integrity (an arcing fault could burn through the panel sides, but this should not be confused with the high energy arcing fault type fires)).
−
– To expedite the process, an average number of vertical segments may be used for such cabinets as motor control centers and DC distribution panels. 
+
 
−
In this context, the term “well-sealed” means there are no open or unsealed penetrations, there are no ventilation openings, and potential warping of the sides/walls of the panel would not open gaps that might allow an internal fire to escape. “Robustly secured” means that any doors and/or  
+
– Free-standing electrical cabinets should be counted by their vertical segments. NUREG/CR-6850 (EPRI 1011989) provided guidance to count cabinets in a “typical” or visible vertical section configuration, however additional guidance was necessary for panels with “atypical” configuration where the guidance for vertical segments could be interpreted in different ways. FAQ 06-0016 was proposed to clarify guidance on electrical panel/cabinet counting for fire frequency.  
−
access panels are all fully and mechanically secured and will not create openings or gaps due to warping during an internal fire. For example, a panel constructed of sheet metal sides “tack welded” to a metal frame would not be considered well-sealed because internal heating would warp the side panels allowing fire to escape through the resulting gaps between weld points. A panel with a simple twist-handle latch mechanism would not be considered robustly secured because the twist handle would not prevent warping of the door under fire conditions. In contrast, a water-tight panel whose door/access panel is bolted in place or secured by mechanical bolt-on clamps around its perimeter would be considered both well-sealed and robustly secured.  Also note that panels that house circuit voltages of 440V or greater are counted because an arcing fault could compromise panel integrity (an arcing fault could burn through the panel sides, but this should not be confused with the high energy arcing fault type fires).  
+
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
−
|  
+
[https://www.epri.com/#/pages/product/000000000001019259/?lang=en-US FAQ 06-0016, Section 3 of Supplement 1]
−
|
+
| 3.43E-02
−
| 3.00E-02
+
| [https://www.epri.com/#/pages/product/000000003002016051/ NUREG-2230 / EPRI 3002016051]
−
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
 
 
|-
 
|-
 
| 16.a
 
| 16.a
 
| Plant-Wide Components
 
| Plant-Wide Components
 
| High Energy Arcing Faults - Low Voltage Electrical Cabinets (480-1000 V)
 
| High Energy Arcing Faults - Low Voltage Electrical Cabinets (480-1000 V)
−
| High-energy arcing faults are associated with switchgear and load centers operating between 480 and 1000 Volts. For this bin, similar to electrical cabinets, the vertical segments of the switchgear and load centers should be counted.  
+
| High-energy arcing faults are associated with load centers operating between 480 and 1000 Volts. Bin 16.a includes load centers at typical nominal system voltage ranging from 480 VAC to 1000 VAC but also includes system voltages down to 440 VAC.
−
| Each vertical segment of the switchgear and load center for low voltage (480-1000 V) electrical cabinets is counted separately. MCCs are not included, unless the MCC is associated with switchgear that is used directly to operate equipment such as load centers.
+
 
−
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
+
Note: In 2023, new HEAF guidance was published. The prior guidance remains an acceptable approach. For prior HEAF bin descriptions, counting guidance, counting reference, fire ignition frequency, and fire ignition frequency reference please see [https://firepra.epri.com/index.php?title=FirePRA:Prior_HEAF_Guidance Prior HEAF counting guidance]
−
[https://www.epri.com/#/pages/product/000000000001019259/?lang=en-US FAQ 06-0017, Section 4 of Supplement 1]
+
| Only count load center supply circuit breakers for HEAF susceptibility - this is the most likely location of a load center HEAF. Do not assign a HEAF count to load centers without bus supply circuit breakers.  
−
| 1.52E-04
+
| [https://www.epri.com/research/products/000000003002025942 EPRI 3002025942 / NUREG-2262]
−
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
+
| 5.32E-04
 +
| [https://www.epri.com/research/products/000000003002025942 EPRI 3002025942 / NUREG-2262]
 
|-
 
|-
 
| 16.b
 
| 16.b
 
| Plant-Wide Components
 
| Plant-Wide Components
 
| High Energy Arcing Faults - Medium Voltage Electrical Cabinets (>1000 V)
 
| High Energy Arcing Faults - Medium Voltage Electrical Cabinets (>1000 V)
−
| High-energy arcing faults are associated with switchgear and load centers. Switchyard transformers and isolation phase buses are not part of this bin. For this bin, similar to electrical cabinets, the vertical segments of the switchgear and load centers should be counted. Additionally, to cover potential explosive failure of oil filled transformers (those transformers that are associated with 4.16 or 6.9kV switchgear and load centers) may be included in vertical segment counts of the switchgear.  
+
| High-energy arcing faults associated with medium-voltage switchgear.  
−
| Each vertical segment of the switchgear and load center for medium voltage (above 1000 V) electrical cabinets is counted separately.
+
 
−
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
+
Note: In 2023, new HEAF guidance was published. The prior guidance remains an acceptable approach. For prior HEAF bin descriptions, counting guidance, counting reference, fire ignition frequency, and fire ignition frequency reference please see [https://firepra.epri.com/index.php?title=FirePRA:Prior_HEAF_Guidance Prior HEAF counting guidance]
−
[https://www.epri.com/#/pages/product/000000000001019259/?lang=en-US FAQ 06-0017, Section 4 of Supplement 1]
+
| Each switchgear bank is counted as one. 
−
| 2.13E-03
+
 
−
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
+
Medium-voltage switchgear should be counted by the entire switchgear bank (e.g., an entire bank is counted as one.
 +
 
 +
Because switchgear's physical and electrical functions may differ, the plant one-line diagram should be reviewed to assist in defining switchgear banks. In some cases, the switchgear physically appears as a single bank, but electrically functions as two adjacent banks (i.e., the main bus bars of each bank are separated). If the banks are electrically separated but appear as one they should be counted individually.  
 +
 
 +
In addition to apportioning via switchgear bank, a MV switchgear weighting factor is also applied to the plant-wide 16.b frequency (see Section 5.2.2.3 of NUREG-2262 for full details). The MV switchgear weighting factor applies 86% of the Bin 16.b frequency to Zone 1. The remaining 14% of the Bin 16.b frequency is applied to Zone 2. If Zone 2 does not have MV switchgear, then use the entire frequency for Zone 1.  
 +
| [https://www.epri.com/research/products/000000003002025942 EPRI 3002025942 / NUREG-2262]
 +
| 1.98E-03
 +
Zone 1: 1.70E-03
 +
Zone 2: 2.77E-04
 +
| [https://www.epri.com/research/products/000000003002025942 EPRI 3002025942 / NUREG-2262]
 
|-
 
|-
−
| 16.1
+
| 16.1-1
 
| Plant-Wide Components
 
| Plant-Wide Components
−
| HEAF for segmented bus ducts
+
| HEAF for segmented (non-segregated) bus ducts (Zones BDUAT and BDSAT)
−
| "A bus duct where the bus bars are made up of multiple sections bolted together at regular intervals (transition points). Here, the bus bars are contained within open-ended sections of metal covers that are bolted together to form a continuous grounded enclosure running the full distance between termination points.
+
| HEAFs associated with segmented bus ducts located in Zone BDUAT and Zone BDSAT.  
−
Segmented bus ducts are able to accommodate tap connections to supply multiple equipment termination points.
 
−
–  Segmented bus ducts tend to be longer in comparison to the nonsegmented bus ducts. Segmented bus ducts are used in cases where the required lengths and/or geometries
 
−
make the use of nonsegmented bus ducts impractical.
 
−
– The length of each segment may vary depending on supplier and installation details.
 
−
– Segmented bus ducts tend to connect end devices that are remote from each other. Example: A segmented bus duct might be used to connect an oil-filled transformer
 
−
located in an outdoor area to equipment (e.g., switchgear) located inside the plant buildings.
 
  
−
Note: This bin does not cover nonsegmented or continuous bus ducts or cable ducts. The arc faults for these two categories are inherently included in the treatment of the end device, and no further treatment is needed. "
+
Consistent with NUREG/CR-6850, Supplement 1, because NSBD (category 1) and cable ducts (category 3) have no transition points other than the termination at the end device, treatment of bus duct faults independent from the treatment of fire for the end device is not required. That is arc faults for categories 1 and 3 of bus ducts are inherently included in the treatment of the end device and no further treatment is needed.  
−
| "The analyst will need to choose between one of two recommended practices for counting segmented bus ducts as a fire ignition source. The choice will be dependent on whether or not the transition points can be identified based on an external visual inspection of the bus duct.  
 
  
−
Counting approach 1: If the transition points along the length of the segmented bus duct can be identified by external visual inspection, or based on plant electrical construction drawings, then
+
Note: In 2023, new HEAF guidance was published. The prior guidance remains an acceptable approach. For prior HEAF bin descriptions, counting guidance, counting reference, fire ignition frequency, and fire ignition frequency reference please see [https://firepra.epri.com/index.php?title=FirePRA:Prior_HEAF_Guidance Prior HEAF counting guidance]
−
count the total number of transition points. Note that transition point counting excludes the bus end termination points, which are considered a part of the end device for fire frequency purposes.
+
| The analyst will need to choose between one of two counting practices; for known transition points (see Section 5.2.3.1 of NUREG-2262 for full details) or for unknown transition points (see Section 5.2.3.2 for full details). The choice will be dependent on whether or not the transition points can be identified.  
−
Transition points may be identifiable based on visual observation or review of design drawings. Transition points for the bus bars may, or may not, correspond to junctions in the outer ducting
 
−
that surrounds the bus bars. It is not intended that the protective duct be removed to identify transition points.
 
  
−
However, industry feedback indicates that the joints or junctions in the outer ducting surrounding a bus duct cannot be assumed to correspond to junctions in the bus bars themselves without
+
Counting approach 1 (For Known Transition Points): The counting is based on the total number of transition points within the bin (identified by external visual inspection or based on plant electrical construction drawings). Although transition points may not be generally known, certain locations may point to the presence of a transition point (e.g., geometric factors such as horizontal direction change or changes in elevation suggest the presence of a transition point).  
−
confirmation. A representative sample of plant applications should be inspected to ensure that the internal bus bar transition points and external duct junctions do in fact align with each other.
 
−
Once the total count of transition points has been obtained, the plant-wide fire frequency is then partitioned to a specific location based on the number of transition points in the location of
 
−
interest divided by the total number of transition points for the entire plant.
 
  
−
Counting approach 2: If the transition points cannot be identified based on external visual inspection, or by plant electrical construction drawings, then the partitioning of fire frequency to
+
Counting approach 2 (For Unknown Transition Points): Based on the total length of the segmented bus duct within the bin. A per-linear-foot frequency can then be estimated by dividing the plant-wide frequency by the total length of segmented bus duct within the bin.  
−
a specific fire scenario is based on apportioning of the fire frequency equally along the length of the bus duct. Hence, the analysis must estimate the total length of segmented bus duct present in
 
−
the plant under analysis. A “per linear foot” fire frequency can then be estimated by dividing the plant-wide fire frequency by the total length of segmented bus duct in the plant.
 
  
−
That is, the fire frequency for a given fire scenario would be based on the ratio of the length of duct for which identified targets fall within the bus duct arc fault zone of influence (see
+
| [https://www.epri.com/research/products/000000003002025942 EPRI 3002025942 / NUREG-2262]
−
discussion below for a definition of the zone of influence) to the total length of bus duct in the plant. A lower limit to the assumed fire frequency for any given fire scenario is also applied.
+
[https://www.epri.com/#/pages/product/000000000001019259/?lang=en-US FAQ 07-0035, Section 7 of Supplement 1]
−
That is, if the length of bus duct for which the identified target(s) fall within the zone of influence is less than 12 linear feet, then a minimum length of 12 feet should be assumed. This
+
| 2.61E-03
−
lower bound is based on the assumption that, lacking specific information on segment lengths, a nominal segment length of 12 feet should be assumed. Any single scenario is then assigned a fire
+
| [https://www.epri.com/research/products/000000003002025942 EPRI 3002025942 / NUREG-2262]
−
frequency equivalent to that associated with one bus bar segment 12 feet in length (i.e., equivalent to one nominal transition point)."
+
|-
 +
|-
 +
| 16.1-2
 +
| Plant-Wide Components
 +
| HEAF for segmented (non-segregated) bus ducts (Zones BD1, BD2, and BDLV)
 +
| HEAFs associated with segmented bus ducts located in Zone BD1, Zone BD2, and Zone LVBD
 +
 
 +
Note: In 2023, new HEAF guidance was published. The prior guidance remains an acceptable approach. For prior HEAF bin descriptions, counting guidance, counting reference, fire ignition frequency, and fire ignition frequency reference please see [https://firepra.epri.com/index.php?title=FirePRA:Prior_HEAF_Guidance Prior HEAF counting guidance]
 +
| The analyst will need to choose between one of two counting practices; for known transition points (see Section 5.2.3.1 of NUREG-2262 for full details) or for unknown transition points (see Section 5.2.3.2 for full details). The choice will be dependent on whether or not the transition points can be identified.  
 +
 
 +
Counting approach 1 (For Known Transition Points): The counting is based on the total number of transition points within the bin (identified by external visual inspection or based on plant electrical construction drawings). Although transition points may not be generally known, certain locations may point to the presence of a transition point (e.g., geometric factors such as horizontal direction change or changes in elevation suggest the presence of a transition point).  
  
−
| [https://www.epri.com/#/pages/product/000000000001019259/?lang=en-US FAQ 07-0035, Section 7 of Supplement 1]
+
Counting approach 2 (For Unknown Transition Points): Based on the total length of the segmented bus duct within the bin. A per-linear-foot frequency can then be estimated by dividing the plant-wide frequency by the total length of segmented bus duct within the bin.
−
| 1.10E-03
+
| [https://www.epri.com/research/products/000000003002025942 EPRI 3002025942 / NUREG-2262]
−
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
+
[https://www.epri.com/#/pages/product/000000000001019259/?lang=en-US FAQ 07-0035, Section 7 of Supplement 1]
 +
| 8.98E-04
 +
| [https://www.epri.com/research/products/000000003002025942 EPRI 3002025942 / NUREG-2262]
 
|-
 
|-
 
| 16.2
 
| 16.2
 
| Plant-Wide Components
 
| Plant-Wide Components
 
| HEAF for iso-phase bus ducts
 
| HEAF for iso-phase bus ducts
−
| A bus duct where the bus bars for each phase are separately enclosed in their own protective housing. The use of iso-phase buses is generally limited to the bus work connecting the main generator to the main transformer.
+
| A bus duct where the bus bars for each phase are separately enclosed in their own protective housing (segregated bus ducts). The primary use of iso-phase buses is generally limited to the bus work connecting the main generator to the main and auxiliary transformers.
 +
 
 +
In 2023, new HEAF guidance was published. The prior guidance remains an acceptable approach. For prior HEAF bin descriptions, counting guidance, counting reference, fire ignition frequency, and fire ignition frequency reference please see [https://firepra.epri.com/index.php?title=FirePRA:Prior_HEAF_Guidance Prior HEAF counting guidance]
 
| There should generally be one iso-phase bus per unit (an iso-phase bus includes all three phases). If there is more than one iso-phase bus, simply count the total number of iso-phases buses per unit. For individual fire scenarios, the plant-wide frequency is applied (i.e. partitioned) equally to each end of each iso-phase bus duct counted.  
 
| There should generally be one iso-phase bus per unit (an iso-phase bus includes all three phases). If there is more than one iso-phase bus, simply count the total number of iso-phases buses per unit. For individual fire scenarios, the plant-wide frequency is applied (i.e. partitioned) equally to each end of each iso-phase bus duct counted.  
−
| [https://www.epri.com/#/pages/product/000000000001019259/?lang=en-US FAQ 07-0035, Section 7 of Supplement 1]
+
| [https://www.epri.com/research/products/000000003002025942 EPRI 3002025942 / NUREG-2262]
−
| 5.91E-04
+
[https://www.epri.com/#/pages/product/000000000001019259/?lang=en-US FAQ 07-0035, Section 7 of Supplement 1]
−
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
+
| 1.01E-03
 +
| [https://www.epri.com/research/products/000000003002025942 EPRI 3002025942 / NUREG-2262]
 
|-
 
|-
 
| 17
 
| 17
Line 271: Line 291:
 
| Hydrogen Tanks
 
| Hydrogen Tanks
 
| Hydrogen storage tanks are generally well-defined items. Multitank hydrogen trailers, because they are interconnected, should be counted as one unit.  
 
| Hydrogen storage tanks are generally well-defined items. Multitank hydrogen trailers, because they are interconnected, should be counted as one unit.  
−
| Each hydrogen tank shall be counted separately.  Multitank hydrogen trailers shall be counted separately.
+
| Each hydrogen tank should be counted separately.  Multitank hydrogen trailers should be counted separately.
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
| 4.93E-03
 
| 4.93E-03
Line 280: Line 300:
 
| Junction Boxes
 
| Junction Boxes
 
| Generally, a junction box is defined as a fully enclosed metal box containing terminals for joining or splicing cables. The box must be fully enclosed with metal panels or welded together but not necessarily well sealed. Cables entering or exiting the junction box should be in metal conduits and have mechanical connections to the metal box.  The junction box should include only terminals for joining and splicing cables. For a full definition, refer to FAQ 13-0006.  
 
| Generally, a junction box is defined as a fully enclosed metal box containing terminals for joining or splicing cables. The box must be fully enclosed with metal panels or welded together but not necessarily well sealed. Cables entering or exiting the junction box should be in metal conduits and have mechanical connections to the metal box.  The junction box should include only terminals for joining and splicing cables. For a full definition, refer to FAQ 13-0006.  
−
| Each junction box shall be counted separately. For junction boxes that are not identified in the cable and raceway database, the number of junction boxes in a specific PAU can be assumed to be proportional to the ratio of the number of junction boxes to conduits in a representative, comparable PAU and the cable loading associated with the location.
+
| The number of junction boxes may be difficult to determine. The frequency can be apportioned based on ratio of cables in the area to the total cable in the plant. Therefore, the ignition source-weighting factor of the cables may be used for this bin as well.
 +
 
 +
As an alternative (described in FAQ 13-0006), the frequency of junction box fires in each fire compartment can be apportioned based on the number of junction boxes in the fire compartment divided by the total number of junction boxes in the plant as determined by the cable and raceway database system or when the cable and raceway database cannot provide this information, the number of junction boxes may be estimated in each fire compartment. See FAQ 13-0006 for full guidance.  
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
[https://www.nrc.gov/docs/ML1333/ML13331B213.pdf FAQ 13-0006]
 
[https://www.nrc.gov/docs/ML1333/ML13331B213.pdf FAQ 13-0006]
Line 290: Line 312:
 
| Miscellaneous Hydrogen Fires
 
| Miscellaneous Hydrogen Fires
 
| This bin includes hydrogen fires in miscellaneous systems other than hydrogen cylinder storage, generator cooling, and battery rooms. It is not necessary to count the ignition sources related to this bin.
 
| This bin includes hydrogen fires in miscellaneous systems other than hydrogen cylinder storage, generator cooling, and battery rooms. It is not necessary to count the ignition sources related to this bin.
−
| Each system found in miscellaneous hydrogen systems shall be counted separately.  This does not include hydrogen cylinder storage, generator cooling, and battery rooms.  An alternative is to not count the ignition sources related to this bin and to establish an ignition frequency associated with the components of this bin for a specific compartment or a pipe segment.
+
| Each system found in miscellaneous hydrogen systems should be counted separately.  This does not include hydrogen cylinder storage, generator cooling, and battery rooms.  An alternative is to not count the ignition sources related to this bin and to establish an ignition frequency associated with the components of this bin for a specific compartment or a pipe segment.
  
 
NOTE: It is important to have a clear definition of system boundaries to ensure that, between this bin and Bin 34, all hydrogen-carrying items of the plant are properly accounted for.
 
NOTE: It is important to have a clear definition of system boundaries to ensure that, between this bin and Bin 34, all hydrogen-carrying items of the plant are properly accounted for.
Line 312: Line 334:
 
| This bin includes pumps and large hydraulic valves. Due to a lack of sufficient statistical data, a separate bin was not defined for large valves that include hydraulic fluid powered mechanisms. It is recommended such valves (e.g. Main Steam Isolation Valves, and Turbine Stop Valves) be counted and included in the pump bin.  
 
| This bin includes pumps and large hydraulic valves. Due to a lack of sufficient statistical data, a separate bin was not defined for large valves that include hydraulic fluid powered mechanisms. It is recommended such valves (e.g. Main Steam Isolation Valves, and Turbine Stop Valves) be counted and included in the pump bin.  
 
| Each pump with a rating greater than 5 hp should be counted separately (do not count pumps with a horsepower rating of 5 hp or below).
 
| Each pump with a rating greater than 5 hp should be counted separately (do not count pumps with a horsepower rating of 5 hp or below).
 +
 +
NUREG&#8209;2178 Volume&nbsp;2 / EPRI&nbsp;3002016052 extends the guidance in FAQ&nbsp;07&#8209;0031 to Bin&nbsp;21. Totally enclosed motors should be excluded from the count because the motor housing would prevent the extension of flames outside the motor casing.
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
[https://www.epri.com/#/pages/product/000000000001019259/?lang=en-US FAQ 07-0031, Section 6 of Supplement 1]
 
[https://www.epri.com/#/pages/product/000000000001019259/?lang=en-US FAQ 07-0031, Section 6 of Supplement 1]
 +
 +
[https://epri.box.com/s/mwlc5vvkmk91rwdw49tdwfh9e2ldeyq2 Description of Treatment for Pump Oil Fires (NRC Recent Fire PRA Methods Review Panel Decisions - Attachment 4)]
 +
 +
[https://epri.box.com/s/tr6kbbgfwjveh3tfzplb1awvmxq0k8gf Fire PRA Methods Review Panel Membership (NRC Recent Fire PRA Methods Review Panel Decisions - Attachment 5)]
 +
 +
[https://epri.box.com/s/0v6yxom7rjun3f6abvct0ww0sul87964 Panel Decision (NRC Recent Fire PRA Methods Review Panel Decisions - Attachment 6)]
 +
 +
[https://www.epri.com/#/pages/product/000000003002016052/ NUREG-2178 Vol 2 / EPRI 3002016052]
 
| 2.72E-02
 
| 2.72E-02
 
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
 
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
Line 329: Line 361:
 
| Plant-Wide Components
 
| Plant-Wide Components
 
| Transformers (oil filled)
 
| Transformers (oil filled)
−
| All indoor transformers that are not an integral part of larger components. Control power transformers and other small transformers, which are subcomponents in electrical equipment, should be ignored.  Examples include 4160V/480V transformers attached to AC load centers, low-voltage regulators, and essential service lighting transformers.  The large yard transformers are not part of this count.  
+
| This bin includes all indoor transformers that are not an integral part of larger components. Control power transformers and other small transformers, which are subcomponents in electrical equipment, should be ignored.  Examples include 4160V/480V transformers attached to AC load centers, low-voltage regulators, and essential service lighting transformers.  The large yard transformers are not part of this count.  
 
| Each indoor oil filled transformers should be counted separately.
 
| Each indoor oil filled transformers should be counted separately.
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
Line 339: Line 371:
 
| Plant-Wide Components
 
| Plant-Wide Components
 
| Transformers (dry)
 
| Transformers (dry)
−
| All indoor transformers that are not an integral part of larger components. Control power transformers and other small transformers, which are subcomponents in electrical equipment, should be ignored.  Examples include 4160V/480V transformers attached to AC load centers, low-voltage regulators, and essential service lighting transformers. Transformers with a 45kVa rating or higher are counted.  The large yard transformers are not part of this count.  
+
| This bin includes all indoor transformers that are not an integral part of larger components. Control power transformers and other small transformers, which are subcomponents in electrical equipment, should be ignored.  Examples include 4160V/480V transformers attached to AC load centers, low-voltage regulators, and essential service lighting transformers. The large yard transformers are not part of this count.  
 
| Each dry transformer with a rating greater than 45 kVa should be counted separately.
 
| Each dry transformer with a rating greater than 45 kVa should be counted separately.
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
Line 376: Line 408:
 
| This category includes components such as air conditioning units, chillers, fan motors, air filters, dampers, etc.  A fan motor and compressor housed in the same component are counted as one component.  Do not count ventilation fans if the drive motor is 5 hp or less.  
 
| This category includes components such as air conditioning units, chillers, fan motors, air filters, dampers, etc.  A fan motor and compressor housed in the same component are counted as one component.  Do not count ventilation fans if the drive motor is 5 hp or less.  
 
| Each component with a rating greater than 5 HP should be counted separately.
 
| Each component with a rating greater than 5 HP should be counted separately.
 +
 +
NUREG&#8209;2178 Volume&nbsp;2 / EPRI&nbsp;3002016052 extends the guidance in FAQ&nbsp;07&#8209;0031 to Bin&nbsp;26. Totally enclosed motors should be excluded from the count because the motor housing would prevent the extension of flames outside the motor casing.
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
−
[https://www.epri.com/#/pages/product/000000000001019259/?lang=en-US FAQ 07-0031, Section 6 of Supplement 1]   
+
 
 +
[https://www.epri.com/#/pages/product/000000000001019259/?lang=en-US FAQ 07-0031, Section 6 of Supplement 1]
 +
 
 +
[https://www.epri.com/#/pages/product/000000003002016052/ NUREG-2178 Vol 2 / EPRI 3002016052]   
 
| 1.64E-02
 
| 1.64E-02
 
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
 
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
Line 393: Line 430:
 
| Transformer Yard
 
| Transformer Yard
 
| Transformer - Non Catastrophic
 
| Transformer - Non Catastrophic
−
| "Similar to Bin 27 this bin includes the high-voltage power transformers typically installed in the yard. However, isolation phase bus ducts are not included in this bin.   
+
| Similar to Bin 27 this bin includes the high-voltage power transformers typically installed in the yard. However, isolation phase bus ducts are not included in this bin.   
−
In a non-catastrophic transformer failure oil does not spill outside transformer tank and the fire does not necessarily propagate beyond the fire source transformer. Analyst can use all the frequency and assume total loss of the “Transformer/Switch Yard” or may split this frequency equally among the large transformers of the area and assume loss of each transformer separately. Loss of offsite power should be determined based on the function of the affected transformer(s)."
+
In a non-catastrophic transformer failure oil does not spill outside transformer tank and the fire does not necessarily propagate beyond the fire source transformer. The analyst can use all the frequency and assume total loss of the “Transformer/Switch Yard” or may split this frequency equally among the large transformers of the area and assume loss of each transformer separately. Loss of offsite power should be determined based on the function of the affected transformer(s).
 
| Each high-voltage power transformer installed in the yard is counted separately.
 
| Each high-voltage power transformer installed in the yard is counted separately.
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
Line 427: Line 464:
 
[https://www.nrc.gov/docs/ML1234/ML12346A488.pdf FAQ 12-0064]
 
[https://www.nrc.gov/docs/ML1234/ML12346A488.pdf FAQ 12-0064]
  
−
[https://www.nrc.gov/docs/ML1725/ML17258A687.html FPRA-FAQ 16-0010]
+
[https://www.nrc.gov/docs/ML1725/ML17258A687.html FAQ 16-0010]
 
| 3.47E-04
 
| 3.47E-04
 
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
 
| [https://www.epri.com/#/pages/product/000000003002002936/?lang=en  EPRI 3002002936 (NUREG-2169)]
Line 444: Line 481:
 
| Turbine Generator Excitor
 
| Turbine Generator Excitor
 
| The turbine generator excitor is a well-defined item. Generally, there is only one excitor per unit.   
 
| The turbine generator excitor is a well-defined item. Generally, there is only one excitor per unit.   
−
| Each turbine generator excitor shall be counted separately.
+
| Each turbine generator excitor should be counted separately.
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
| [https://www.epri.com/#/pages/product/000000000001011989/?lang=en-US EPRI 1011989 / NUREG/CR-6850]
 
| 8.36-04
 
| 8.36-04
Line 496: Line 533:
 
|}
 
|}
  
−
'''Table 6-2'''
+
'''Table 6-2: Summary Description of Transient Fire Influencing Factors (as updated in FAQ 12-0064)'''
−
 
 
−
'''Summary Description of Transient Fire Influencing Factors (as updated in FAQ 12-0064)'''
 
 
{| class="wikitable"
 
{| class="wikitable"
 
|-
 
|-
Line 630: Line 665:
 
|-
 
|-
 
| High (10)
 
| High (10)
−
| Applicable for compartments where  
+
| Applicable for compartments where:
 
(1) combustible/flammable materials are sometimes brought in and left in either open containers for a short time or in a closed container, but outside a dedicated fire-safe cabinet for an extended time.   
 
(1) combustible/flammable materials are sometimes brought in and left in either open containers for a short time or in a closed container, but outside a dedicated fire-safe cabinet for an extended time.   
  
Line 664: Line 699:
 
(6) entry is prohibited without health physics or radiation protection technician present,
 
(6) entry is prohibited without health physics or radiation protection technician present,
 
(7) entry is prohibited without a fire watch, and/or
 
(7) entry is prohibited without a fire watch, and/or
−
(8) personnel safety tag-outs are required to lock out an automatic suppression system (e.g., Halon or CO2) prior to entry or prior to conducting a maintenance activity.  
+
(8) personnel safety tag-outs are required to lock out an automatic suppression system (e.g., Halon or CO<sub>2</sub>) prior to entry or prior to conducting a maintenance activity.  
  
 
<span style='font-size:90%>'''Note 4: Equipment requiring maintenance:'''
 
<span style='font-size:90%>'''Note 4: Equipment requiring maintenance:'''
Line 682: Line 717:
  
 
<span style='font-size:90%>'''Note 8: MCR hot work:'''
 
<span style='font-size:90%>'''Note 8: MCR hot work:'''
−
The ranking of 0.1 for the MCR requires that a review of plant records confirms that no violations of, or exceptions to, the MCR hot work restrictions while at power have been recorded over some reasonable prior time period (i.e., five years). }}
+
The ranking of 0.1 for the MCR requires that a review of plant records confirms that no violations of, or exceptions to, the MCR hot work restrictions while at power have been recorded over some reasonable prior time period (i.e., five years).
−
 
 
−
==Related EPRI 1011989 NUREG/CR-6850 Appendices==
 
−
Appendix C, Appendix for Chapter 6, Determination of Generic Fire Frequencies
 
−
 
 
−
Appendix F, Appendix for Chapter 8, Walkdown Forms
 
  
 
==Supplemental Guidance==
 
==Supplemental Guidance==
  
−
===FAQ 06-0016: EPRI 1019259 NUREG/CR-6850 Supplement 1, Chapter 3===
+
See Wiki Tables 6-1 and 6-2 for the most recent ignition source bins, counting guidance, and fire ignition frequencies.
−
''Ignition Source Counting Guidance for Electrical Cabinets (FAQ 06-0016)'' 
 
−
 
 
−
Relevant Correspondence:
 
−
*FAQ 06-0016, Rev. 1 (ADAMS Accession No. ML070580334)
 
−
*Closure Memo, FAQ 06-0016, Counting Electrical Panels and Cabinets, dated October 5, 2007 (ADAMS Accession No. ML072700475)
 
−
 
 
−
NUREG/CR-6850 (EPRI 1011989) provided guidance to count cabinets in a “typical” or visible vertical section configuration, however additional guidance was necessary for panels with “atypical” configuration where the guidance for vertical segments could be interpreted in different ways. FAQ 06-0016 was proposed to clarify guidance on electrical panel/cabinet counting for fire frequency.
 
−
 
 
−
'''Impact on EPRI 1011989 NUREG/CR-6850 Guidance'''
 
−
 
 
−
This guidance in FAQ 06-0016 provides clarification on the fire ignition frequency counting application listed in Section 6.5.6 Bin 15, page 6-16.
 
−
 
 
−
Examples:
 
−
Detailed examples of counting electrical cabinets are provided in Section 3.2 of NUREG/CR-6850 Supplement 1. It is important to note that the counting methodology described in Section 3.2 of NUREG/CR-6850 Supplement 1, doesn’t require a volumetric comparison. Nonetheless, the classification of electrical enclosures in NUREG-2178, Vol. 1, although is consistent and does not affect the existing ignition source counting information available in Chapter 6 of NUREG/CR-6850 and applicable fire PRA FAQs, it requires a volumetric size analysis for asigning HRR probabilities distributions.
 
−
 
 
−
 
 
−
===FAQ 06-0017: EPRI 1019259 NUREG/CR-6850 Supplement 1, Chapter 4===
 
−
''Ignition Source Counting Guidance for High-Energy Arcing Faults (FAQ 06-0017)''
 
−
 
 
−
Relevant Correspondence:
 
−
* FAQ 06-0017, Rev. 2 (ADAMS Accession No. ML071570255)
 
−
* Closure Memo, FAQ 06-0017, Clarifying/Enhancing Guidance for Counting High Energy Arcing Faults, dated September 26, 2007 (ADAMS Accession No. ML072500300)
 
−
 
 
−
NUREG/CR-6850 (EPRI 1011989) provided guidance for treatment of high energy arcing faults, however inconsistency in the application of the treatment was observed. FAQ 06-0017 was proposed to clarify guidance on high energy arcing fault counting for partitioning of the fire ignition frequency task.  The FAQ provides guidance for counting arcing faults based on panel voltages. In addition, the FAQ provides guidance to exclude MCCs from arcing fault counting.
 
−
 
 
−
'''Impact on EPRI 1011989 NUREG/CR-6850 Guidance'''
 
−
 
 
−
This guidance in FAQ 06-0017 provides clarification on the fire ignition frequency counting application listed in Section 6.5.6 Bin 16, page 6-16.
 
−
 
 
−
Examples:
 
−
Let's assume there is a total of fifty (50) vertical sections associated with HEAFs in a plant.  Thirty (30) out of the fifty (50) sections are classified as HEAF for Low-Voltage Panels (Bin 16.a)  and the remaining twenty (20) vertical sections are classified as HEAF for Medium-Voltage Panels (Bin 16.b). Therefore, per Table 4-6 in NUREG 2169, the generic frequency that should be applied (i.e., partitioned) equally to the vertical sections classified as HEAF for Low-Voltage Panels (counted as thirty in this example) is 1.52E-04 and the generic frequency that should be applied (i.e., partitioned) equally to the vertical sections classified as HEAF for Medium-Voltage Panels (counted as twenty in this example) is 2.13E-03.
 
−
 
 
−
 
 
−
 
 
−
===FAQ 06-0018: EPRI 1019259 NUREG/CR-6850 Supplement 1, Chapter 5===
 
−
''Ignition Source Counting Guidance for Main Control Board (MCB) (FAQ 06-0018)''
 
−
 
 
−
Relevant Correspondence:
 
−
* FAQ 06-0018,  Rev. 1 (ADAMS Accession No. ML070800079)
 
−
* Closure Memo, FAQ 06-0018, Rev 1 Ignition Source Counting Guidance for Main Control Boards, dated September 26, 2007 (ADAMS Accession No. ML072500273)
 
−
 
 
−
NUREG/CR-6850 (EPRI 1011989) provided guidance for the main control board in Appendix L, however the applicability to Task 6, Bin 4 was unclear. FAQ 06-0018 was proposed to clarify guidance on determining the definition of the main control board for fire ignition frequency and Appendix L applications.
 
−
 
 
−
'''Impact on EPRI 1011989 NUREG/CR-6850 Guidance'''
 
−
 
 
−
This guidance in FAQ 06-0018 provides clarification on the fire ignition frequency counting application listed in Section 6.5.6 Bin 4 (i.e., the main control board), page 6-15.
 
−
Examples:
 
−
 
 
−
MCB (Bin 4) counting includes:
 
−
* Horseshoe, and
 
−
* Other detached panels  like “bench-board” (also referred as “consoles”) which are:
 
−
** Serving as  panels that were detached serving as an integral part of the main plant monitoring and control functions;
 
−
** Located in the center of the operators’ main work area; and 
 
−
** Manned on a nearly continuous basis.
 
−
 
 
−
Other “back panels” and detached panels housing items such as balance-of-plant and off-site power controls and indicators should be excluded from the main control board and treated as general electrical panels (Bin 15). The conditions of the MCB rear side to be treated as part of the MCB are detailed in See Section 8.2.10.
 
−
 
 
−
 
 
−
===FAQ 07-0031: EPRI 1019259 NUREG/CR-6850 Supplement 1, Chapter 6===
 
−
''Miscellaneous Fire Ignition Frequency Binning Issues (FAQ 07-0031)''
 
−
 
 
−
Relevant Correspondence:
 
−
* FAQ 07-0031, Rev. 0 (ADAMS Accession No. ML071380238)
 
−
* Closure Memo, FAQ 07-0031, Rev 1 Clarification of Miscellaneous Ignition Source Binning Issues, dated December 17, 2007 (ADAMS Accession No. ML072840658)
 
−
 
 
−
NUREG/CR-6850 (EPRI 1011989) provided guidance on electrical equipment counting, however the FAQ was intended to provide a more consistent basis for counting of miscellaneous electrical equipment. FAQ 07-0031 was proposed to clarify guidance for several ignition source bins to include electrical motors (Bin 14), pumps (Bin 21), transformers (Bin 23), and ventilation subsystems (bin 26).  The FAQ also provided guidance on eliminating motors and transformers from ignition source counting based on size or function.
 
−
 
 
−
'''Impact on EPRI 1011989 NUREG/CR-6850 Guidance'''
 
−
 
 
−
This guidance in FAQ 07-0031 provides clarification on the fire ignition frequency counting application listed in Section 6.5.6 Bins 14, 21, 23, and 26, pages 6-16 and 6-18.
 
−
 
 
−
Examples:
 
−
* Electric Motors (Bin 14) counting includes: any electric motor with a rating greater than 5 hp, unless the motor meets at least one of the two following exclusionary provisions:
 
−
** Motors that are attached to equipment already identified and counted in other bins.
 
−
** Motors, including MOV drive motors, which are totally enclosed regardless of the motor size.
 
−
* Pumps (Bin 21) counting includes: pumps rated above 5 hp.
 
−
* Transformers (Bin 23) counting includes: all dry-type transformers with a rating greater than 45 kVA and all oil-filled transformers.
 
−
* Ventilation Subsystems (Bin 26) counting includes:  any ventilation subsystem (air conditioning units, chillers, fan motors, air filters, dampers, etc.) with an electric motor greater than 5 hp.
 
−
 
 
−
The electric motors, pumps and ventilation subsystems rated 5 hp or less and the dry transformers with a rating greater than 45 kVA should be excluded.
 
−
 
 
−
 
 
−
===FAQ 07-0035: EPRI 1019259 NUREG/CR-6850 Supplement 1, Chapter 7===
 
−
''Bus Duct (Counting) Guidance for High-Energy Arcing Faults (FAQ 07-0035)''
 
−
 
 
−
Relevant Correspondence:
 
−
* FAQ 07-0035, Rev. 2 (ADAMS Accession No. ML071650151)
 
−
* Closure Memo, FAQ 07-0035, Rev 1 Bus Duct Counting Guidance for High Energy Arcing Faults, dated July 16, 2009 (ADAMS Accession No. ML091620572)
 
−
 
 
−
NUREG/CR-6850 (EPRI 1011989) provided guidance for treatment of high energy arcing faults in switchgear and load centers, however is absent of guidance for bus duct fires. FAQ 07-0035 was proposed to clarify treatment of high energy arcing faults for bus duct failures.  The FAQ provides guidance for counting and fire event frequency for bus ducts.
 
−
 
 
−
'''Impact on EPRI 1011989 NUREG/CR-6850 Guidance'''
 
−
 
 
−
This guidance in FAQ 07-0035 provides clarification on the fire ignition frequency counting application listed in Appendix M of NUREG/CR-6850 (EPRI 1011989).
 
−
 
 
−
Examples:
 
−
Non-segmented (or continuous) bus ducts and cable ducts): There is no transition points other than the terminations at the end device, so no treatment (no counting) of bus duct faults/fires independent from the treatment of fires for the end devices is required.
 
−
 
 
−
Iso-phase bus ducts (Bin 16.2): Count the total number of iso-phase buses (an iso-phase bus includes all three phases) per unit. For individual fire scenarios, the plant-wide frequency is applied (i.e., partitioned) equally to each end of each iso-phase duct counted. For example, typically there is one (1) iso-phase bus per unit in a plant, therefore there are 2 ends for the iso-phase duct counted. In this case, the generic frequency that should be applied (i.e., partitioned) equally to the ends of each iso-phase duct (counted as two for the unit in this example) is 5.91E-0, per Table 4-6 in NUREG-2169.
 
−
 
 
−
Segmented bus ducts (Bin 16.1):
 
−
 
 
−
Counting approach 1: If the transition points along the length of the segmented bus duct can be identified by external visual inspection, or based on plant electrical construction drawings, then count the total number of transition points. The transition point counting excludes the bus end termination points, which are considered a part of the end device for fire frequency purposes.  For example, let's assume there are seven (7) transitions point in a segmented bus duct, in addition to the bus end termination points. In this case, the generic frequency that should be applied (i.e., partitioned) equally to the transition points of the segmented bus duct (counted as seven in this example) is 1.10E-03, per Table 4-6 in NUREG 2169.
 
−
 
 
−
Counting approach 2: If the transition points cannot be identified based on external visual inspection, or by plant electrical construction drawings, then the partitioning of fire frequency to a specific fire scenario is based on apportioning of the fire frequency equally along the length of the bus duct. A “per linear foot” fire frequency can then be estimated by dividing the plant-wide fire frequency by the total length of segmented bus duct in the plant.  That is, the fire frequency for a given fire scenario would be based on the ratio of the length of duct for which identified targets fall within the bus duct arc fault zone of influence,  to the total length of bus duct in the plant.
 
−
 
 
−
For example, let's assume there is a forty (40) feet long segmented bus duct in a unit that could affect two targets (A and B). Target A falls within the zone of influence of twenty-five (25) m long of the bus duct and target B within fifteen (15) m long. In this case the generic frequency (1.10E-03, per Table 4-6 in NUREG 2169) should be applied (i.e., apportioned) proportionally to the segmented bus duct length related to each target. That is  25/40 times the plant-wide fire frequency for target A and 15/40 times the plant-wide fire frequency for target B.
 
−
 
 
−
Finally a lower limit to the assumed fire frequency for any given fire scenario is also applied. That is, if the length of bus duct for which the identified target(s) fall within the zone of influence is less than 12 linear feet, then a minimum length of 12 feet should be assumed. Following the above example, let's assume there is a forty (40) feet long segmented bus duct in a unit that could affect two targets (A and B). Target A falls within a zone of influence of ten (10) m along the length of the bus duct and target B within forty (40) m along the length of the bus duct. In this case the generic frequency (1.10E-03, per Table 4-6 in NUREG 2169) should be applied (i.e., apportioned) proportionally to the segmented bus duct length related to each target, but a minimum length of 12 feet should be assumed for the shortest segment. That is  12/40 times the plant-wide fire frequency for target A and the remaining frequency (28/40) times the plant-wide fire frequency for target B.
 
−
 
 
−
'''Additional Considerations'''
 
−
 
 
−
FAQ 07-0035 provides additional guidance for characterizing the zone of influence, or damage, for bus duct fires as part of NUREG/CR-6850 (EPRI 1011989) Chapter 11 fire modeling guidance.
 

Latest revision as of 12:20, 20 January 2025

Task Overview

Background

This task describes the approach to develop frequency estimates for fire compartments and scenarios. Significant changes from the EPRI FIVE method have been made in this task. The changes generally relate to use of challenging events, considerations associated with data quality, and increased use of a fully component based ignition frequency model (as opposed to the location/component-based model used, for example, in FIVE).

Purpose

This section describes the procedure for estimating the fire-ignition frequencies associated with fire ignition sources. Generic ignition frequencies that can be specialized to plant conditions in terms of plant characteristics and plant fire event experience are provided. Uncertainties in the generic frequencies are also provided in terms of 5th, 50th, and 95th percentiles.

Scope

This work package addresses the following fire-ignition frequency related issues:

  • Plant specific fire event data review and generic fire frequency update using Bayesian approach,
  • Equipment (ignition source) count by compartment,
  • Apportioning of ignition frequencies according to compartment-specific configurations, and
  • Uncertainty considerations in the fire frequencies.

Related Element of ASME/ANS PRA Standard

Fire Ignition Frequency (IGN)

Related EPRI 1011989 NUREG/CR-6850 Appendices

Appendix C, Appendix for Chapter 6, Determination of Generic Fire Frequencies

Appendix F, Appendix for Chapter 8, Walkdown Forms

Current FPRA Counting Guidance and Fire Ignition Frequencies

Table 6-1 presents relevant information such as bin, ignition source, counting guidance, and mean fire ignition frequency for ignition sources counted in the Fire PRA. In many cases, the counting guidance provided in NUREG/CR-6850 has been supplemented by additional guidance including formally published in NUREG/CR-6850 Supplement 1 and through the frequently asked questioned (FAQ) process. Links to the counting guidance is provided in the "Counting Reference" column. Similarly, the fire ignition frequencies published in NUREG/CR-6850 are no longer the most current. A second set of fire ignition frequencies was published in NUREG/CR-6850 Supplement 1 (Chapter 10, FAQ 08-0048). A memo on May 14, 2015 from the NRC, clarified that the fire ignition frequencies in NUREG/CR-6850 Supplement 1 (FAQ 08-0048) should be replaced with the most current guidance in EPRI 3002002936 (NUREG-2169).

Table 6-1: Fire Ignition Sources, Counting Guidance, and Ignition Frequencies

Bin Plant Location Ignition Source Description Count (how) Counting Reference Fire Ignition Frequency (Mean) Fire Ignition Frequency Reference
1 Battery Room Batteries Each bank of interconnected sets of batteries located in one place (often referred to as Battery Room). Interconnected sets of batteries is counted as one. Cells may not be counted individually. EPRI 1011989 / NUREG/CR-6850 1.96E-04 EPRI 3002002936 (NUREG-2169)
2 Containment (PWR) Reactor Coolant Pump The reactor coolant pumps (RCPs) are distinct devices in PWRs that vary between two and four, depending on primary loop design. Each reactor coolant pump is counted separately. EPRI 1011989 / NUREG/CR-6850 1.37E-03 EPRI 3002002936 (NUREG-2169)
3 Containment (PWR) Transients and Hotwork General transient combustibles and hotwork activities located in Containment (PWR). The ignition source weighting factor of transient fires is estimated using a ranking scheme that takes into account maintenance activities, occupancy level, and storage of flammable materials. These steps are outlined in FAQ 12-0064 Section 6.5.7.2. The introduction of developing transient influence factors for smaller spaces than fire compartments is discussed in FAQ 14-0007. EPRI 1011989 / NUREG/CR-6850

FAQ 12-0064

FAQ 14-0007

4.21E-04 EPRI 3002002936 (NUREG-2169)
4 Control Room Main Control Board A control room typically consists of one or two (depending on the number of units) main control boards as the central element of the room. Each main control board, typically consisting of the main horseshoe and nothing else, is counted separately. This bin may also include "benchboard" panels that are detached from, but directly in front of, the main horseshoe (at some plants such panels are referred to as "consoles"). FAQ-14-0008 also clarified that the rear side of the MCB may be treated as part of the MCB if both the rear and front sides are connected together as a single enclosure (including a continuous overhead, or by an overhead with penetrations or vents along it longitudinally, cabinet ceiling, or cables connecting the front and back sides of the MCB). EPRI 1011989 / NUREG/CR-6850

FAQ 06-0018, Section 5 of Supplement 1

FAQ 14-0008

2.05E-3 NUREG-2178 Vol 2 / EPRI 3002016052
5 Control/Aux/Reactor Building Cable fires caused by welding and cutting For this bin, it is assumed that all exposed cables (i.e., cables that are not in conduits or wrapped by noncombustible materials) have an equal likelihood of experiencing a fire caused by welding and cutting across the entire location (Control Building, Auxiliary Building, or Reactor Building). The ignition source weighting factor of cable fires caused by welding and cutting is estimated using the hot work factor and cable quantity in the fire compartment. The hot work ranking factors are described in Table 6-2 (as updated in FAQ 12-0064). Guidance for this bin is updated in FAQ 12-0064 Section 6.5.7.2 and Fire PRA FAQ 16-0010. The hot work factor is then weighed in combination with a relative numerical estimate of the quantity of cables in the location to the total quantity of cables in the entire location set to generate the final location weighting factor. The cable quantity (either total weight or total combustible load) is typically reported in the Fire Hazards Analysis (FHA). EPRI 1011989 / NUREG/CR-6850

FAQ 12-0064

FAQ 16-0010

7.83E-04 EPRI 3002002936 (NUREG-2169)
6 Control/Aux/Reactor Building Transient fires caused by welding and cutting Transient fires due to hotwork activities located in the Control Building, Auxiliary Building, or Reactor Building. The ignition source weighting factor of transient fires caused by welding and cutting is estimated using a ranking scheme that takes into account the hot work factor. The hot work ranking factors are described in Table 6-2 (as updated in FAQ 12-0064). Guidance for this bin is updated in FAQ 12-0064 Section 6.5.7.2 and Fire PRA FAQ 14-0007 (distributing transient influence factors for smaller spaces than fire compartments). EPRI 1011989 / NUREG/CR-6850

FAQ 12-0064

FAQ 14-0007

4.44E-03 EPRI 3002002936 (NUREG-2169)
7 Control/Aux/Reactor Building Transients General transient combustibles or activities located in the Control Building, Auxiliary Building, or Reactor Building. The ignition source weighting factor of transient fires is estimated using a ranking scheme that takes into account maintenance activities, occupancy level, and storage of flammable materials. These steps are outlined in FAQ 12-0064 Section 6.5.7.2. Developing transient influence factors for smaller spaces than fire compartments is discussed in FAQ 14-0007. EPRI 1011989 / NUREG/CR-6850

FAQ 12-0064

FAQ 14-0007

3.33E-03 EPRI 3002002936 (NUREG-2169)
8 Diesel Generator Room Diesel Generators Diesel generators are generally well-defined items that include a set of auxiliary subsystems associated with each engine. All diesel generators that are included in the electric power recovery model should be counted here. In addition to the normal safety related diesel generators, this may include the Technical Support Center diesel generators, Security diesel generators, etc. It is recommended that each diesel generator and its subsystems be counted as one unit. The subsystems may include diesel generator air start compressors, air receiver, batteries and fuel storage, and delivery system. Each diesel generator should be counted separately. It is recommended that the electrical cabinets for engine and generator control that stand separate from the diesel generator be included as part of “Plant-Wide Components - Electrical Cabinets.” Control panels that are attached to engine may be counted as part of the engine. EPRI 1011989 / NUREG/CR-6850 7.81E-03 EPRI 3002002936 (NUREG-2169)
9 Plant-Wide Components Air Compressors This bin covers the large air compressors that provide plant instrument air included in the Internal Events PRA Model. These compressors are generally well-defined devices. They may include an air receiver, air dryer, and control panel attached to the compressor. These items should be considered part of the air compressor. If portable compressors are part of the model, those compressors should also be included in the equipment count for this bin. Air compressors are generally well-defined devices (and includes portable units credited in the PRA model). The air compressor skid, which could include an air receiver, air dryer, and control panel attached to the compressor, should be counted as one, as they are considered to be part of the air compressor. NOTE: Compressors associated with the ventilation systems and small air compressors used for specialized functions are NOT part of this bin. EPRI 1011989 / NUREG/CR-6850 4.69E-03 EPRI 3002002936 (NUREG-2169)
10 Plant-Wide Components Battery Chargers These are generally well defined items associated with DC buses. Each battery charger should be counted separately. EPRI 1011989 / NUREG/CR-6850 1.12E-03 EPRI 3002002936 (NUREG-2169)
11 Plant-Wide Components Cable fires caused by welding and cutting For this bin, it is assumed that all exposed cables (i.e., cables that are not in conduits or wrapped by noncombustible materials) have an equal likelihood of experiencing a fire caused by welding and cutting across the entire location (located in the Power Block, but not in the Control Building, Auxiliary Building, Reactor Building, Turbine Building, or Containment (PWR)). The ignition source weighting factor of cable fires caused by welding and cutting is estimated using the hot work factor and cable quantity in the fire compartment. The hot work ranking factors are described in Table 6-2 (as updated in FAQ 12-0064). Guidance for this bin is updated in FAQ 12-0064 Section 6.5.7.2 and Fire PRA FAQ 16-0010. The hot work factor is then weighed in combination with a relative numerical estimate of the quantity of cables in the location to the total quantity of cables in the entire location set to generate the final location weighting factor. The cable quantity (either total weight or total combustible load) is typically reported in the Fire Hazards Analysis (FHA). EPRI 1011989 / NUREG/CR-6850

FAQ 12-0064

FAQ 16-0010

2.77E-04 EPRI 3002002936 (NUREG-2169)
12 Plant-Wide Components Cable Run (self-ignited cable fires) Self-ignited cables fires postulated in fire compartments with unqualified cables only or a mix of qualified cables and unqualified cables. The cable loading of each compartment should be established using the same approach as that for Bin 5, except that, in this case, all plant fire compartments should be taken into account. The cable quantity (either total weight or total combustible load) is typically reported in the Fire Hazards Analysis (FHA). For rooms where detailed fire modeling is necessary FAQ 13-0005 provides guidance on how to calculate a scenario level ignition frequency (by dividing the quantity of cables in the tray on fire by the total quantity of cable in the room).

Consistent with Appendix R of EPRI 1011989, self-ignited cable fire only need to be postulated in compartments which contain unqualified cable types.

EPRI 1011989 / NUREG/CR-6850

FAQ 13-0005

FAQ 16-0010

7.02E-04 EPRI 3002002936 (NUREG-2169)
13 Plant-Wide Components Dryers Clothes dryers are generally well-defined units. Each clothes dryer is counted separately. EPRI 1011989 / NUREG/CR-6850 3.66E-03 EPRI 3002002936 (NUREG-2169)
14 Plant-Wide Components Electric Motors Electrical motors with a power rating greater than 5hp associated with various devices, not including those counted in other bins, are included in this bin. This may include elevator motors, valve motors, etc. Motors (not included those counted in other bins) with a rating greater than 5 HP are counted. Totally enclosed motors should be excluded from the count because the motor housing would prevent the extension of flames outside the motor casing. See FAQ 07-0031 for the additional guidance. EPRI 1011989 / NUREG/CR-6850

FAQ 07-0031, Section 6 of Supplement 1

5.43E-03 EPRI 3002002936 (NUREG-2169)
15 Plant-Wide Components Electrical Cabinets Electrical cabinets represent such items as switchgears, motor control centers, DC distribution panels, relay cabinets, control and switch panels (excluding panels that are part of machinery), fire protection panels, etc.
Electrical cabinets in a nuclear power plant vary significantly in size, configuration, and voltage. Size variation range from small-wall mounted units to large walk-through vertical control cabinets, which can be 20’ to 30’ long. The configuration can vary based on number of components that contribute to ignition, such as relays and circuit cards, and combustible loading, which also affects the fire frequency. Voltages in electrical cabinets vary from low voltage (120 V) panels to 6.9 kV switchgear. Even though it is expected that these features affect the likelihood of fire ignition, from a simple analysis of the event data involving the electrical cabinets, it was determined that the variation by cabinet type did not warrant separate frequency evaluation. Therefore, one fire frequency was estimated for the electrical cabinets.

The following rules should be used for counting electrical cabinets:

– Simple wall-mounted panels housing less than four switches may be excluded from the counting process,

– Well-sealed electrical cabinets that have robustly secured doors (and/or access panels) and that house only circuits below 440V should be excluded from the counting process, (In this context, the term “well-sealed” means there are no open or unsealed penetrations, there are no ventilation openings, and potential warping of the sides/walls of the panel would not open gaps that might allow an internal fire to escape. “Robustly secured” means that any doors and/or access panels are all fully and mechanically secured and will not create openings or gaps due to warping during an internal fire. For example, a panel constructed of sheet metal sides “tack welded” to a metal frame would not be considered well-sealed because internal heating would warp the side panels allowing fire to escape through the resulting gaps between weld points. A panel with a simple twist-handle latch mechanism would not be considered robustly secured because the twist handle would not prevent warping of the door under fire conditions. In contrast, a water-tight panel whose door/access panel is bolted in place or secured by mechanical bolt-on clamps around its perimeter would be considered both well-sealed and robustly secured. Also note that panels that house circuit voltages of 440V or greater are counted because an arcing fault could compromise panel integrity (an arcing fault could burn through the panel sides, but this should not be confused with the high energy arcing fault type fires)).

– Free-standing electrical cabinets should be counted by their vertical segments. NUREG/CR-6850 (EPRI 1011989) provided guidance to count cabinets in a “typical” or visible vertical section configuration, however additional guidance was necessary for panels with “atypical” configuration where the guidance for vertical segments could be interpreted in different ways. FAQ 06-0016 was proposed to clarify guidance on electrical panel/cabinet counting for fire frequency.

EPRI 1011989 / NUREG/CR-6850

FAQ 06-0016, Section 3 of Supplement 1

3.43E-02 NUREG-2230 / EPRI 3002016051
16.a Plant-Wide Components High Energy Arcing Faults - Low Voltage Electrical Cabinets (480-1000 V) High-energy arcing faults are associated with load centers operating between 480 and 1000 Volts. Bin 16.a includes load centers at typical nominal system voltage ranging from 480 VAC to 1000 VAC but also includes system voltages down to 440 VAC.

Note: In 2023, new HEAF guidance was published. The prior guidance remains an acceptable approach. For prior HEAF bin descriptions, counting guidance, counting reference, fire ignition frequency, and fire ignition frequency reference please see Prior HEAF counting guidance

Only count load center supply circuit breakers for HEAF susceptibility - this is the most likely location of a load center HEAF. Do not assign a HEAF count to load centers without bus supply circuit breakers. EPRI 3002025942 / NUREG-2262 5.32E-04 EPRI 3002025942 / NUREG-2262
16.b Plant-Wide Components High Energy Arcing Faults - Medium Voltage Electrical Cabinets (>1000 V) High-energy arcing faults associated with medium-voltage switchgear.

Note: In 2023, new HEAF guidance was published. The prior guidance remains an acceptable approach. For prior HEAF bin descriptions, counting guidance, counting reference, fire ignition frequency, and fire ignition frequency reference please see Prior HEAF counting guidance

Each switchgear bank is counted as one.

Medium-voltage switchgear should be counted by the entire switchgear bank (e.g., an entire bank is counted as one.

Because switchgear's physical and electrical functions may differ, the plant one-line diagram should be reviewed to assist in defining switchgear banks. In some cases, the switchgear physically appears as a single bank, but electrically functions as two adjacent banks (i.e., the main bus bars of each bank are separated). If the banks are electrically separated but appear as one they should be counted individually.

In addition to apportioning via switchgear bank, a MV switchgear weighting factor is also applied to the plant-wide 16.b frequency (see Section 5.2.2.3 of NUREG-2262 for full details). The MV switchgear weighting factor applies 86% of the Bin 16.b frequency to Zone 1. The remaining 14% of the Bin 16.b frequency is applied to Zone 2. If Zone 2 does not have MV switchgear, then use the entire frequency for Zone 1.

EPRI 3002025942 / NUREG-2262 1.98E-03

Zone 1: 1.70E-03 Zone 2: 2.77E-04

EPRI 3002025942 / NUREG-2262
16.1-1 Plant-Wide Components HEAF for segmented (non-segregated) bus ducts (Zones BDUAT and BDSAT) HEAFs associated with segmented bus ducts located in Zone BDUAT and Zone BDSAT.

Consistent with NUREG/CR-6850, Supplement 1, because NSBD (category 1) and cable ducts (category 3) have no transition points other than the termination at the end device, treatment of bus duct faults independent from the treatment of fire for the end device is not required. That is arc faults for categories 1 and 3 of bus ducts are inherently included in the treatment of the end device and no further treatment is needed.

Note: In 2023, new HEAF guidance was published. The prior guidance remains an acceptable approach. For prior HEAF bin descriptions, counting guidance, counting reference, fire ignition frequency, and fire ignition frequency reference please see Prior HEAF counting guidance

The analyst will need to choose between one of two counting practices; for known transition points (see Section 5.2.3.1 of NUREG-2262 for full details) or for unknown transition points (see Section 5.2.3.2 for full details). The choice will be dependent on whether or not the transition points can be identified.

Counting approach 1 (For Known Transition Points): The counting is based on the total number of transition points within the bin (identified by external visual inspection or based on plant electrical construction drawings). Although transition points may not be generally known, certain locations may point to the presence of a transition point (e.g., geometric factors such as horizontal direction change or changes in elevation suggest the presence of a transition point).

Counting approach 2 (For Unknown Transition Points): Based on the total length of the segmented bus duct within the bin. A per-linear-foot frequency can then be estimated by dividing the plant-wide frequency by the total length of segmented bus duct within the bin.

EPRI 3002025942 / NUREG-2262

FAQ 07-0035, Section 7 of Supplement 1

2.61E-03 EPRI 3002025942 / NUREG-2262
16.1-2 Plant-Wide Components HEAF for segmented (non-segregated) bus ducts (Zones BD1, BD2, and BDLV) HEAFs associated with segmented bus ducts located in Zone BD1, Zone BD2, and Zone LVBD

Note: In 2023, new HEAF guidance was published. The prior guidance remains an acceptable approach. For prior HEAF bin descriptions, counting guidance, counting reference, fire ignition frequency, and fire ignition frequency reference please see Prior HEAF counting guidance

The analyst will need to choose between one of two counting practices; for known transition points (see Section 5.2.3.1 of NUREG-2262 for full details) or for unknown transition points (see Section 5.2.3.2 for full details). The choice will be dependent on whether or not the transition points can be identified.

Counting approach 1 (For Known Transition Points): The counting is based on the total number of transition points within the bin (identified by external visual inspection or based on plant electrical construction drawings). Although transition points may not be generally known, certain locations may point to the presence of a transition point (e.g., geometric factors such as horizontal direction change or changes in elevation suggest the presence of a transition point).

Counting approach 2 (For Unknown Transition Points): Based on the total length of the segmented bus duct within the bin. A per-linear-foot frequency can then be estimated by dividing the plant-wide frequency by the total length of segmented bus duct within the bin.

EPRI 3002025942 / NUREG-2262

FAQ 07-0035, Section 7 of Supplement 1

8.98E-04 EPRI 3002025942 / NUREG-2262
16.2 Plant-Wide Components HEAF for iso-phase bus ducts A bus duct where the bus bars for each phase are separately enclosed in their own protective housing (segregated bus ducts). The primary use of iso-phase buses is generally limited to the bus work connecting the main generator to the main and auxiliary transformers.

In 2023, new HEAF guidance was published. The prior guidance remains an acceptable approach. For prior HEAF bin descriptions, counting guidance, counting reference, fire ignition frequency, and fire ignition frequency reference please see Prior HEAF counting guidance

There should generally be one iso-phase bus per unit (an iso-phase bus includes all three phases). If there is more than one iso-phase bus, simply count the total number of iso-phases buses per unit. For individual fire scenarios, the plant-wide frequency is applied (i.e. partitioned) equally to each end of each iso-phase bus duct counted. EPRI 3002025942 / NUREG-2262

FAQ 07-0035, Section 7 of Supplement 1

1.01E-03 EPRI 3002025942 / NUREG-2262
17 Plant-Wide Components Hydrogen Tanks Hydrogen storage tanks are generally well-defined items. Multitank hydrogen trailers, because they are interconnected, should be counted as one unit. Each hydrogen tank should be counted separately. Multitank hydrogen trailers should be counted separately. EPRI 1011989 / NUREG/CR-6850 4.93E-03 EPRI 3002002936 (NUREG-2169)
18 Plant-Wide Components Junction Boxes Generally, a junction box is defined as a fully enclosed metal box containing terminals for joining or splicing cables. The box must be fully enclosed with metal panels or welded together but not necessarily well sealed. Cables entering or exiting the junction box should be in metal conduits and have mechanical connections to the metal box. The junction box should include only terminals for joining and splicing cables. For a full definition, refer to FAQ 13-0006. The number of junction boxes may be difficult to determine. The frequency can be apportioned based on ratio of cables in the area to the total cable in the plant. Therefore, the ignition source-weighting factor of the cables may be used for this bin as well.

As an alternative (described in FAQ 13-0006), the frequency of junction box fires in each fire compartment can be apportioned based on the number of junction boxes in the fire compartment divided by the total number of junction boxes in the plant as determined by the cable and raceway database system or when the cable and raceway database cannot provide this information, the number of junction boxes may be estimated in each fire compartment. See FAQ 13-0006 for full guidance.

EPRI 1011989 / NUREG/CR-6850

FAQ 13-0006

3.61E-03 EPRI 3002002936 (NUREG-2169)
19 Plant-Wide Components Miscellaneous Hydrogen Fires This bin includes hydrogen fires in miscellaneous systems other than hydrogen cylinder storage, generator cooling, and battery rooms. It is not necessary to count the ignition sources related to this bin. Each system found in miscellaneous hydrogen systems should be counted separately. This does not include hydrogen cylinder storage, generator cooling, and battery rooms. An alternative is to not count the ignition sources related to this bin and to establish an ignition frequency associated with the components of this bin for a specific compartment or a pipe segment.

NOTE: It is important to have a clear definition of system boundaries to ensure that, between this bin and Bin 34, all hydrogen-carrying items of the plant are properly accounted for.

EPRI 1011989 / NUREG/CR-6850 4.82E-03 EPRI 3002002936 (NUREG-2169)
20 Plant-Wide Components Off-gas/H2 Recombiner (BWR) Generally there are at least two recombiner systems per BWR. Each recombiner system should be counted as one unit. EPRI 1011989 / NUREG/CR-6850 5.81E-03 EPRI 3002002936 (NUREG-2169)
21 Plant-Wide Components Pumps and large hydraulic valves This bin includes pumps and large hydraulic valves. Due to a lack of sufficient statistical data, a separate bin was not defined for large valves that include hydraulic fluid powered mechanisms. It is recommended such valves (e.g. Main Steam Isolation Valves, and Turbine Stop Valves) be counted and included in the pump bin. Each pump with a rating greater than 5 hp should be counted separately (do not count pumps with a horsepower rating of 5 hp or below).

NUREG‑2178 Volume 2 / EPRI 3002016052 extends the guidance in FAQ 07‑0031 to Bin 21. Totally enclosed motors should be excluded from the count because the motor housing would prevent the extension of flames outside the motor casing.

EPRI 1011989 / NUREG/CR-6850

FAQ 07-0031, Section 6 of Supplement 1

Description of Treatment for Pump Oil Fires (NRC Recent Fire PRA Methods Review Panel Decisions - Attachment 4)

Fire PRA Methods Review Panel Membership (NRC Recent Fire PRA Methods Review Panel Decisions - Attachment 5)

Panel Decision (NRC Recent Fire PRA Methods Review Panel Decisions - Attachment 6)

NUREG-2178 Vol 2 / EPRI 3002016052

2.72E-02 EPRI 3002002936 (NUREG-2169)
22 Plant-Wide Components RPS MG Sets In PWRs, the RPS MG sets are well-defined devices. Each RPS MG set is counted separately. Electrical cabinets associated with the RPS MG set should not be counted, as they are considered to be part of the RPS MG set. EPRI 1011989 / NUREG/CR-6850 2.31E-03 EPRI 3002002936 (NUREG-2169)
23a Plant-Wide Components Transformers (oil filled) This bin includes all indoor transformers that are not an integral part of larger components. Control power transformers and other small transformers, which are subcomponents in electrical equipment, should be ignored. Examples include 4160V/480V transformers attached to AC load centers, low-voltage regulators, and essential service lighting transformers. The large yard transformers are not part of this count. Each indoor oil filled transformers should be counted separately. EPRI 1011989 / NUREG/CR-6850

FAQ 07-0031, Section 6 of Supplement 1

9.56E-03 EPRI 3002002936 (NUREG-2169)
23b Plant-Wide Components Transformers (dry) This bin includes all indoor transformers that are not an integral part of larger components. Control power transformers and other small transformers, which are subcomponents in electrical equipment, should be ignored. Examples include 4160V/480V transformers attached to AC load centers, low-voltage regulators, and essential service lighting transformers. The large yard transformers are not part of this count. Each dry transformer with a rating greater than 45 kVa should be counted separately. EPRI 1011989 / NUREG/CR-6850

FAQ 07-0031, Section 6 of Supplement 1

9.56E-03 EPRI 3002002936 (NUREG-2169)
24 Plant-Wide Components Transient fires caused by welding and cutting Transient fires due to hotwork activities located in the Power Block, but not in the Control Building, Auxiliary Building, Reactor Building, Turbine Building, or Containment (PWR). The ignition source weighting factor of transient fires caused by welding and cutting is estimated using a ranking scheme that takes into account the hot work factor. The hot work ranking factors are described in Table 6-2 (as updated in FAQ 12-0064). Guidance for this bin is updated in FAQ 12-0064 Section 6.5.7.2 and Fire PRA FAQ 14-0007 (distributing transient influence factors for smaller spaces than fire compartments). EPRI 1011989 / NUREG/CR-6850

FAQ 12-0064

FAQ 14-0007

4.79E-03 EPRI 3002002936 (NUREG-2169)
25 Plant-Wide Components Transients General transient combustibles or activities located in the Power Block, but not in the Control Building, Auxiliary Building, Reactor Building, Turbine Building, or Containment (PWR). The ignition source weighting factor of transient fires is estimated using a ranking scheme that takes into account maintenance activities, occupancy level, and storage of flammable materials. These steps are outlined in FAQ 12-0064 Section 6.5.7.2. The introduction of developing transient influence factors for smaller spaces than fire compartments is discussed in FAQ 14-0007. EPRI 1011989 / NUREG/CR-6850

FAQ 12-0064

FAQ 14-0007

8.54E-03 EPRI 3002002936 (NUREG-2169)
26 Plant-Wide Components Ventilation Subsystems This category includes components such as air conditioning units, chillers, fan motors, air filters, dampers, etc. A fan motor and compressor housed in the same component are counted as one component. Do not count ventilation fans if the drive motor is 5 hp or less. Each component with a rating greater than 5 HP should be counted separately.

NUREG‑2178 Volume 2 / EPRI 3002016052 extends the guidance in FAQ 07‑0031 to Bin 26. Totally enclosed motors should be excluded from the count because the motor housing would prevent the extension of flames outside the motor casing.

EPRI 1011989 / NUREG/CR-6850

FAQ 07-0031, Section 6 of Supplement 1

NUREG-2178 Vol 2 / EPRI 3002016052

1.64E-02 EPRI 3002002936 (NUREG-2169)
27 Transformer Yard Transformer - Catastrophic The high-voltage power transformers typically installed in the yard belong to this bin. They include plant output power transformers, auxiliary-shutdown transformers, and startup transformers, etc. Isolation phase bus ducts are also included in this bin to simplify fire frequency analysis. Each high-voltage power transformer installed in the yard is counted separately. EPRI 1011989 / NUREG/CR-6850 6.61E-03 EPRI 3002002936 (NUREG-2169)
28 Transformer Yard Transformer - Non Catastrophic Similar to Bin 27 this bin includes the high-voltage power transformers typically installed in the yard. However, isolation phase bus ducts are not included in this bin.

In a non-catastrophic transformer failure oil does not spill outside transformer tank and the fire does not necessarily propagate beyond the fire source transformer. The analyst can use all the frequency and assume total loss of the “Transformer/Switch Yard” or may split this frequency equally among the large transformers of the area and assume loss of each transformer separately. Loss of offsite power should be determined based on the function of the affected transformer(s).

Each high-voltage power transformer installed in the yard is counted separately. EPRI 1011989 / NUREG/CR-6850 6.53E-03 EPRI 3002002936 (NUREG-2169)
29 Transformer Yard Yard Transformers (Others) Items associated with yard transformers but not the transformers themselves (e.g., oil power output cables) are part of this bin. In the screening phase of the project, the analyst may conservatively assign the same frequency to all the items in this group. If the scenario would not screen out, the frequency may then be divided among the various items in this group. A relative ranking scheme may be used for this purpose. The ranking may be based on the relative characteristics of the items and analysts’ judgment. Items associated with yard transformers but not the transformers themselves (e.g., oil power output cables) are counted separately. EPRI 1011989 / NUREG/CR-6850 3.69E-03 EPRI 3002002936 (NUREG-2169)
30 Turbine Building Boiler Boilers are generally well-defined items. Each boiler should be counted separately. All ancillary items associated with each boiler may be included as part of the boiler. Control panels that are installed separate from a boiler may be included in the “Electrical Cabinets (Plant-Wide Components)” bin. EPRI 1011989 / NUREG/CR-6850 1.09E-03 EPRI 3002002936 (NUREG-2169)
31 Turbine Building Cable fires caused by welding and cutting For this bin, it is assumed that all exposed cables (i.e., cables that are not in conduits or wrapped by noncombustible materials) have an equal likelihood of experiencing a fire caused by welding and cutting across the entire location (Turbine Building). The ignition source weighting factor of cable fires caused by welding and cutting is estimated using the hot work factor and cable quantity in the fire compartment. The hot work ranking factors are described in Table 6-2 (as updated in FAQ 12-0064). Guidance for this bin is updated in FAQ 12-0064 Section 6.5.7.2 and Fire PRA FAQ 16-0010. The hot work factor is then weighed in combination with a relative numerical estimate of the quantity of cables in the location to the total quantity of cables in the entire location set to generate the final location weighting factor. The cable quantity (either total weight or total combustible load) is typically reported in the Fire Hazards Analysis (FHA). EPRI 1011989 / NUREG/CR-6850

FAQ 12-0064

FAQ 16-0010

3.47E-04 EPRI 3002002936 (NUREG-2169)
32 Turbine Building Main Feedwater Pumps Main feedwater pumps are generally well-defined entities. Main feedwater pumps are generally well-defined entities. Ancillary components associated with each pump are considered a part of the pump and should not be counted separately. EPRI 1011989 / NUREG/CR-6850 4.38E-03 EPRI 3002002936 (NUREG-2169)
33 Turbine Building Turbine Generator Excitor The turbine generator excitor is a well-defined item. Generally, there is only one excitor per unit. Each turbine generator excitor should be counted separately. EPRI 1011989 / NUREG/CR-6850 8.36-04 EPRI 3002002936 (NUREG-2169)
34 Turbine Building Turbine Generator Hydrogen A complex of piping, valves, heat exchangers, oil separators, and often skid-mounted devices are associated with turbine generator hydrogen. A complex of piping, valves, heat exchangers, oil separators, and often skid-mounted devices are associated with turbine generator hydrogen. Consider the entire complex as one system and assign the ignition frequency of this bin to that system. It is important to have a clear definition of system boundaries to ensure that, between this bin and Bin 19, all hydrogen-carrying items of the plant are properly accounted for. Similar to Bin 29, in the screening phase of the project, the analyst may conservatively assign the same frequency to all the items in this bin. If the scenario would not screen out, the frequency may then be divided among the various items using a relative ranking scheme. The ranking may be based on the relative characteristics of the items and the analysts’ judgment.

NOTE: It is important to have a clear definition of system boundaries to ensure that, between this bin and Bin 19, all hydrogen-carrying items of the plant are properly accounted for.

EPRI 1011989 / NUREG/CR-6850 4.12E-03 EPRI 3002002936 (NUREG-2169)
35 Turbine Building Turbine Generator Oil Similar to hydrogen, a complex of oil storage tanks, pumps, heat exchangers, valves, and control devices belong to this bin. A complex of piping, valves, heat exchangers, oil separators, and often skid-mounted devices are associated with turbine generator hydrogen. It is recommended to treat the entire complex as one system and assign the ignition frequency of this bin to that system. Similar to the preceding bin and Bin 29, in the screening phase of the project, the analyst may conservatively assign the same frequency to all the items in this bin. If the scenario would not screen out, the frequency may then be divided among the various items using a relative ranking scheme. The ranking may be based on the relative characteristics of the items and analysts’ judgment. EPRI 1011989 / NUREG/CR-6850 5.49E-03 EPRI 3002002936 (NUREG-2169)
36 Turbine Building Transient fires caused by welding and cutting Transient fires due to hotwork activities located in the Turbine Building. The ignition source weighting factor of transient fires caused by welding and cutting is estimated using a ranking scheme that takes into account the hot work factor. The hot work ranking factors are described in Table 6-2 (as updated in FAQ 12-0064). Guidance for this bin is updated in FAQ 12-0064 Section 6.5.7.2 and Fire PRA FAQ 14-0007 (distributing transient influence factors for smaller spaces than fire compartments). EPRI 1011989 / NUREG/CR-6850

FAQ 12-0064

FAQ 14-0007

4.67E-03 EPRI 3002002936 (NUREG-2169)
37 Turbine Building Transients General transient combustibles or activities located in the Turbine Building. The ignition source weighting factor of transient fires is estimated using a ranking scheme that takes into account maintenance activities, occupancy level, and storage of flammable materials. These steps are outlined in FAQ 12-0064 Section 6.5.7.2. The introduction of developing transient influence factors for smaller spaces than fire compartments is discussed in FAQ 14-0007. EPRI 1011989 / NUREG/CR-6850

FAQ 12-0064

FAQ 14-0007

6.71E-03 EPRI 3002002936 (NUREG-2169)

Table 6-2: Summary Description of Transient Fire Influencing Factors (as updated in FAQ 12-0064)

Influencing Factor Ranking Value (Note 1) Where applicable

General Electro-Mechanical (E/M) Maintenance (excluding hot work)

No (0) Applicable for locations where maintenance activities during power operation are precluded by design and/or operation. (Note 2)
Very Low (0.3) Applicable for locations where:

(1) access is strictly controlled (not just simple key-card type access) (Note 3), and

(2) areas with NO equipment subject to frequent maintenance (Note 4), and

(3) location contains no plant equipment or components other than cables, fire detectors, junction boxes, and other minor plant support equipment.

Requirement: No violations in administrative controls (Note 5).

This rating may not be applied to the MCR but may be applied to the Cable Spreading Room (CSR) devoid of other equipment, and cable vault and tunnel areas meeting the criteria. Other plant locations may also be assigned the "very low" (0.3) ranking factor provided all of the defined criteria are met.

Low (1) Applicable for areas with small number of (preventative maintenance/corrective maintenance) PM/CM work orders compared to the average number of work orders for a typical compartment (Note 6), or

Applicable for general plant locations where strict permitting procedures are enforced, but do not meet the requirements for a “0.3” (very low) rating factor.

Requirement: No violations in administrative controls (Note 5) OR performance monitoring program is in place (Note 7)

Medium (3) Applicable for areas with average number of PM/CM work orders (Note 6).
High (10) Applicable for areas with large number of PM/CM work orders compared to the average number of work orders for a typical compartment (Note 6).
Very High (50) Applicable for areas with significantly more PM/CM work orders compared to the average number of work orders for a typical compartment (Note 6).

Hotwork

No (0) Applicable for areas in which hot work activities during power operation are precluded by design and/or operation (Note 2).
Extremely Low (0.1) Applicable for MCR, if:

(1) plant procedures prohibit hot work in the MCR during power operations, and

(2) no violations in MCR hot work restrictions (Note 8).

Very Low (0.3) Applicable for CSR and cable vault and tunnel areas, provided that:

(1) access to the location is strictly controlled (Note 3),

(2) the location contains no plant equipment or components other than cables, fire detectors, and junction boxes,

(3) hot work during power operations is prohibited by plant procedures, and

(4) no violations in administrative controls (Note 5)

Applicable for MCR, if extremely low ranking of 0.1 is not applicable

Low (1) Applicable for:

(1) Small number of hot work related PM/CM work orders associated with hot work compared to the average number of work orders for a typical compartment (Note 6).

(2) General plant locations where plant procedures generally preclude hot work activities with exceptions subject to the strictest of permitting requirements.

Requirement: No violations in administrative controls (Note 5) OR performance monitoring program is in place (Note 7)

Medium or Average (3) Applicable for average number of hot work related PM/CM work orders (Note 6)
High (10) Applicable for large number of hot work related PM/CM work orders compared to the average number of work orders for a typical compartment (Note 6).
Very High (50) Applicable for plant areas that may experience significantly more PM/CM work orders compared to the average number of work orders for a typical compartment (Note 6).

Occupancy

No (0) Applicable for compartments where entrance is not possible during plant operation (Note 2).
Very Low (0.3) Applicable for:

(1) compartments bounded on all sides by controlled physical barriers and normally unoccupied during plant operations.

(2) compartments not used as an access pathway for any other plant location.

(3) location with access strictly controlled (Note 3).

Low (1) Applicable for compartments with low foot traffic or out of general traffic path.
Medium or Average (3) Applicable for compartments not continuously occupied, but with regular foot traffic.
High (10) Applicable for continuously occupied compartments.

Storage

No (0) Applicable for compartments where entrance is not possible during plant operation (Note 2).
Very Low (0.3) Applicable for:

(1) entire fire areas designated “combustible free zones”, and

(2) areas with no temporary structures built, stored or moved into the vicinity, comprised at least in part of combustible materials (e.g. wooden scaffolding).

Requirement: No violations of administrative controls (Note 5).

Low (1) Applicable for:

(1) compartments where no combustible/flammable materials are stored by practice but where combustibles may be introduced subject to a permitting process, or

(2) compartments where all combustible/flammable material are stored in closed containers and/or placed in dedicated fire-safe cabinets.

Requirement: No violations in administrative controls (Note 5) OR performance monitoring program is in place (Note 7)

Medium or Average (3) Applicable for areas that contain:

(1) small quantities of low-combustibility materials (e.g., solid flame retardant materials) in open storage, or

(2) flammable gasses or liquids stored in approved containers and/or flammable combustible storage cabinets.

High (10) Applicable for compartments where:

(1) combustible/flammable materials are sometimes brought in and left in either open containers for a short time or in a closed container, but outside a dedicated fire-safe cabinet for an extended time.

(2) larger quantities of flammable materials (e.g., radiation protection clothing, packing boxes or materials, paints, flammable liquids, oils) are stored.

Notes regarding Table 6-2

Note 1: Intent of Ranking: The overall intent of the weighting factor method is to reflect real differences in the relative likelihood of transient fires in various locations while at the same time preserving the overall plant-wide fire frequency for each ignition source bin. In application the analyst should consider the following points relative to the intent of the transient location factor ranking method: (1) The ranking factor numerical values assigned to each location should reflect relative weighting values within each applicable frequency bin location set. The relative rankings should not look across location sets. For example, when addressing bins 36 and 37 the analyst should not compare locations of the turbine building (the location set for these two bins) to other non-turbine building locations (e.g., to areas of the control building which is covered by bin 25 and 26). (2) The full range of the numerical ranking values is available to the analyst and should, at least nominally, be exercised for each location set. If the full range of the ranking factor values is not exercised, then fire frequency will be distributed more evenly to the applicable fire compartments. If the analyst concludes that a relatively even distribution is the correct answer for the plant and location set, then it is recommended that an explanation should be provided in the PRA documentation.

Note 2: Access precluded by design and/or operation: Examples of areas where maintenance and hot work activities are precluded by design and/or operation, include the following: (1) inerted locations such as inside an inerted BWR containment during power operation, (2) very high radiation areas such as a traversing in-core probe (TIP) room (or equivalent) for a BWR, (3) permanently sealed cable tunnels such as poured concrete cable ways without access or cable tunnels where access ways have been closed by mortared block, (4) cable tunnels with manhole or hatch access where the manholes/hatches are welded shut; BUT, if an urgent situation could occur that would require cutting into the areas to avoid a shutdown, then value of 0.3 should be assigned (5) areas physically too small to allow personnel access under any conditions (e.g., an underground cable chase), (6) areas with extreme thermal environment beyond human tolerance such as the main steam tunnel in a BWR, and (7) locations where the equipment present occupies all the available space such that the storage or placement of transient materials would be physically impossible. The existence of administrative controls in and of itself is not a compelling basis for a rating of 0.

Note 3: Access strictly controlled: Examples of locations where access is strictly controlled (not just simple key-card type access) are as follows: (1) special entry permitting procedures are in place (e.g., access into containment during power operations would be an involved process), (2) confined space access controls are imposed (i.e., per OSHA requirements), (3) limited personnel access lists are established, (4) extra security controls such as locked doors with limited access keys, (5) verbal notification of entry and exit to security or operations personnel is required in a specific location, (6) entry is prohibited without health physics or radiation protection technician present, (7) entry is prohibited without a fire watch, and/or (8) personnel safety tag-outs are required to lock out an automatic suppression system (e.g., Halon or CO2) prior to entry or prior to conducting a maintenance activity.

Note 4: Equipment requiring maintenance: Examples of equipment that do not require frequent maintenance are the following: cables, fire detectors, junction boxes and other minor plant support equipment such as normal and emergency lighting, access control panels, plant paging or communications equipment, alarms or alarm panels, and security monitoring or support equipment. In general, the presence of any piece of equipment that was counted as a fire ignition source during Step 6 would preclude assignment of “very low” for this factor. Conversely, it cannot be assumed that the lack of countable fire ignition sources implies that the very low ranking factor applies. If equipment items are present that may require maintenance but do not meet the counting criteria (e.g., smaller pumps, motors or ventilation subsystems) then the very low ranking factor would not apply. A rating of 0.3 is applicable to cable spreading rooms (CSR) devoid of other equipment, and cable vault and tunnel areas that have access strictly controlled A rating of 0.3 is not applicable for the Main Control Room.

Note 5: No violations in administrative controls: A rating of 0.3 requires a verification that no violations of the administrative controls related to the influence factor that is being rated (maintenance, hot work, or storage) have occurred over a reasonable prior time period (i.e., five years).

Note 6: Work Orders: The analyst should use engineering judgment to determine the maintenance factor of compartments with no work orders in the selected period of time. The judgment can be based on the characteristics of the compartment relative to compartments with work orders. If the work orders cannot be collected easily, the analyst may use engineering judgment based on personal experience or information gathered from the maintenance personnel of the plant. In this case, the analyst may ask the maintenance personnel to assign a rating number between 0 and 10 in terms of frequency of maintenance at a compartment and to identify the two or three most typical maintenance activities undertaken (e.g., pump overhaul or electrical device replacement).

Note 7: Performance monitoring program: A performance monitoring program is in place and demonstrates that the administrative control programs are meeting expectations and objectives.

Note 8: MCR hot work: The ranking of 0.1 for the MCR requires that a review of plant records confirms that no violations of, or exceptions to, the MCR hot work restrictions while at power have been recorded over some reasonable prior time period (i.e., five years).

Supplemental Guidance

See Wiki Tables 6-1 and 6-2 for the most recent ignition source bins, counting guidance, and fire ignition frequencies.